31
10.2 Address and activate the AUX3 servomotor.
Usually these operations are already set in the manufacturer factory.
They would be necessary in same cases as: the substitution of the servomotor, in case the FGR mode were not activated yet or the LMV5x were be
supplied loose…
WARNING: for LMV52.400 device, in case of FGR servomotor addressing: the only possible choice is AuxActuator3. Don't set
the FGR servomotor for a different one.
1st level
2nd level
3rd level
4th level
5th level
6th level
Description
Params & Display
Actuators
Parameter settings for fuel/ air ratio
control
Addressing
Parameter settings for firing on Gas
or on Oil
AirActuator
GasActuat
OilActuat
AuxActuator
AuxActuator 2
AuxActuator 3
AuxActuator 3
AuxActuator 3 MUST be chosen
After the addressing, activate the FGR servomotor.
1st level
2nd level
3rd level
4th level
5th level
6th level
Description
Params & Display
RatioControl
Parameter settings for fuel/ air ratio
control
GasSettings
OilSettings
Parameter settings for firing on Gas
or on Oil
AuxActuator deactivated
damper act
VSD active
AUX3
VSD+Aux3
Deactivated for LMV52.xxx
AUX3 for LMV51.300
Deactivated for LMV52.xxx
AUX3 for LMV51.300
AirActuator deactivated
activated
air influen
activated
AuxActuator 1
AuxActuator 2
AuxActuator 3
Activated for LMV52.xxx
VSD
GasActuator
OilActuator
Activated
Activated
Choice according to the Operation
mode gas setting or oil setting.
Summary of Contents for HRX2060
Page 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......