PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical Specifications
(**) The distance between the measurement surface and the burner body is 1 meter (UNI EN ISO 3744)
Type
HRX2060
Model
MG. MD. S.
*.
A. 8.
80.
EI.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(8)
1 BURNER TYPE
HRX2060, HRX2080
2 FUEL
G - Light oil, M - Natural gas
3 OPERATION (Available versions)
MD - Fully modulating
4 BLAST TUBE
S - Standard
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard Y - Special
7 EQUIPMENT
1 = 2 gas gas proving system
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
80 = DN80 100 = DN100 125 = DN125
8
MICRO-PROCESSOR CONTROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
EK = with O
2
trim control, with VSD control
HRX2060
HRX2080
Output
min. - max. kW
2500 - 16000
2500 - 19000
Fuel
MG - Natural gas-Light oil
Category
(see next paragraph)
Gas rate min.-max.
min.- max. (Stm
3
/h)
265 - 1693
265 - 2011
Pressure
mbar
(see Note 2)
Light oil rate
min.-max. kg/h
211 - 1349
211 - 1602
Oil viscosity
cSt @ 40 °C
2 - 7,4
Oil density
kg/m
3
840
Oil train inlet pressure
bar
2 max
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
51
61
Pump motor
kW
5,5
5,5
Fan motor power consumption
kW
45
55
Protection
IP40
Operation
MD - Fully modulating
Gas train 80
ØValves / Connection
3” / DN80
3” / DN80
Gas train 100
ØValves / Connection
4” / DN100
4” / DN100
Gas train 125
ØValves / Connection
5” / DN125
5” / DN125
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service
Continuous
Noise level (sound power level)(**)
93
Note1:
All gas flow rates are referred to Stm
3
/h (1.013 mbar absolute pressure, 15° C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ / Stm
3
);
Note2:
Maximum gas pressure = 500mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80 %
Summary of Contents for HRX2060
Page 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......