PART III: OPERATION
40
Oil Flow Rate Settings
1
Once the air and gas flow rates are adjusted, turn the burner off, switch to the oil operation (OIL, on the burner control panel).
2
with the electrical panel open, prime the oil pump acting directly on the related
CP
contactor (see next picture): check the pump
motor rotation and keep pressing for some seconds until the oil circuit is charged;
3
bleed the air from the
M
pressure gauge port by loosing the cap without removing it, then release the contactor.
Fig. 8
4
As for setting the fuel/air ratio curve, see the LMV related manual.
5
Only if necessary, adjust the supply pressure as follows;insert a pressure gauge into the port shown on figure and act on on the
pump adjusting screw
VR
. Pressure values are indicated at the beginning of this paragraph.
6
In order to get the maximum oil flow rate, adjust the pressure (reading its value on the
PG
pressure gauge) without changing the air
flow rate set during the gas operation adjustments (see previous paragraph), checking always the combustion parameters.
Turn the burner off; then start it up again. If the adjustment is not correct, repeat the previous steps.
Suntec T..
Fig. 9
Fig. 10
CP
M
VR
Pressure gauge port
RP
PG
Summary of Contents for HRX2060
Page 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......