7
1.4
Wireway and electrical conduit
The following cables are recommended for separate wiring;
Complete separate from all other cables:
•
Cable for "VSD to Fan motor" Line voltage, see also "1. Frequency inverter / Variable Speed Drive (VSD)"
•
Cable for ignition high voltage, see also "2. Ignition"
•
Cable for the Flame sensors
Together in cable duct 1 for Low voltage, e.g.:
•
Cable
for
CAN-Bus
•
Cable for VSD speed sensor, LMV5 X70
•
Cable for VSD Release & Set point , LMV5 X73
•
Cables for the Load controller: Temperature or Pressure sensor, set point, load output at the LMV5 X60, X61, X62, X63
Together in cable duct 2 for Line voltage, e.g.:
•
Cable for Ignition transformer
•
Cables for other Line voltage signals, e.g. Gas pressure switches, Air pressure switches, ….
•
Cable for Gas valves SKP/VGD
Example of wiring, see next paragraph Wireway and electrical conduit
NOTE: KEEP SEPARATE SIGNALS CABLES, OUTPUT CABLES, PHOTOCELL CABLE AS SHOWN IN THE BELOW PICTURE
The cables from the LMV5 to the SKP/VGD -Gas
vales shall be connected at the LMV5 side with X9-01:
L-Valve1, L-Valve2 and with X9-02, N, PE) and
connected at the SKP side separate to each SKP.
Summary of Contents for HRX2060
Page 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......