PART IV: MAINTENANCE
44
Cleaning/replacing the electrodes (direct ignition)
To remove the oil gun, proceed as follows:
1
remove the combustion head as described on the prevoius paragraph;
2
loosen the
VL
screw and remove the oil gun and the electrodes: check the oil gun, replace it if necessary;
3
after removing the oil gun, unscrew the nozzle and replace it if necessary;
4
in order to replace the electrodes, unscrew the
VE
fixing screws and remove them: place the new electrodes being careful to
observe the measures showed on pag.: reassemlbe following the reversed procedure.
Caution
: adjust the nozzle position according to the air pipe, by means of the
VU
screw, ance the
VL
screw is fastened.
Adjusting the ignition electrode
Replacing the ignition electrode
ATTENTION: avoid the electrodes to get in touch with metallic parts (blast tube, head, etc.), otherwise the boiler
operation would be compromised. Check the electrodes position after any intervention on the combustion head.
ATTENTION: avoid the electrode to get in touch with metallic parts (blast tube, head, etc.), otherwise the boiler
operation would be compromised. Check the electrode position after any intervention on the combustion head.
ATTENTION:
avoid the electrode to get in touch with metallic parts (blast tube, head, etc.), otherwise the boiler operation
would be compromised. Check the electrode position after any intervention on the combustion head.
_
A
B
C
D
HRX2050 MG
3÷4
~14
8
5
HRX2080 MG
3÷4
~14
8
5
HRX3050 MG
3÷4
~14
8
5
D
B
C
A
VU
VL
VE
To replace the ignition electrode, proceed as follows:
1
Remove the burner cover
2
Disconnect the electrode (E) cable (CE)
3
Remove the combustion head (see par. “Removing the combustion head”)
4
Loose screw (B) that fasten the ignition electrode (E) to the burner pilot (P)
5
Remove the electrode and replace it, referring to the values quoted on figure
CE
E
B
P
Ignition pilot electrodes positions (for light oil operation)
ATTENTION:
avoid
the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), otherwise the boi-
ler’s operation would be compromised. Check the electrodes position after any intervention on the combustion head.
Summary of Contents for HRX2060
Page 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......