Overview,
Continued
The AutoPulse Z-10’s NACs can be configured to operate in any of the following ways.
Both NACS turn on and stay on until a Signal Silence is performed. No inhibit.
NAC1 on until Reset; NAC2 on until Signal Silence. No Inhibit.
Both NACs turn on and stay on until a System Reset occurs. No Inhibit.
Both NACS turn on and stay on until a Signal Silence is performed. 60 second inhibit.
NAC1 on until System Reset; NAC2 on until Signal Silence. 60 second inhibit.
Both NACs turn on and stay on until a System Reset occurs. 60 second inhibit.
Selections listed as No Inhibit allow immediate silence or reset; selections listed as 1 Min. Inhibit,
do not allow a silence or reset for one minute following alarm activation.
Note:
For NYC Abort ONLY, all selections are valid, but the selections labeled "NAC1 On til Reset, NAC2 On til
Silence" become "NAC3 On til Reset, NAC1&2 On til Silence." (The inhibit or no inhibit remains valid.) In other
words, when the NYC abort application is selected, choosing “NAC 1 on til Reset, NAC2 On til Silence – No
Inhibit” is equivalent to choosing “NAC3 On til Reset, NAC1&2 On til Silence – No Inhibit."
Method
Description
Text-Based
Programming
The ninth prompt, shown below, asks you to set the NAC Operation.
[09] NAC OPERATION:
d 1 = Both on til Silence with no inhibit
*2 = NAC1 - on til Reset, NAC2 - on til Silence with no inhibit
3 = Both on til Reset with no inhibit
4 = Both on til Silence with 60 sec inhibit
5 = NAC1 - on til Reset, NAC2 - on til Silence with 60 sec inhibit
6 = Both on til Reset with 60 sec inhibit
(d=default, *=current setting)
Select Number(X=exit):
Enter the number corresponding to the value you want to select and press the carriage return. Refer to
“Programming Supervisory Latching Operation” for a description of the next programming step.
Front Panel
Programming
Use the Reset key to scroll through the selections. When the desired choice is illuminated, press the ACK key
to save the selection in memory and move to the next step.
Programming NAC Operation
Overview
Yellow Trouble LED indicates
panel is in programming mode.
Green LED is AC Power.
These LEDs represent the
available options. Use the
RESET key to move through
the choices.
Press ACK when the
illuminated LED corresponds to
the desired choice.
When eighth LED from top on
left side of the display is lit, it
indicates the NAC Operation
option is being programmed.