3-13
Figure 3-8. NAC Field Wiring Connections
For all UL Listed Notification Appliances, NACs are rated Regulated 24V dc, at 1.5A maximum
each. Maximum allowed strobe load 1.35A. The balance of the 3A total capacity for the two
NACs can be auxiliary loads or audible notification appliances.
All other regulated 24V dc synchronized notification appliances require the use of their associated
Listed external synchronization module. Notification Circuit rating is 1.5A maximum, 1.35A
maximum strobe load. Use the UL rated operating current to determine maximum number of
appliances allowed per NAC.