![Tyco AutoPulse Z-10 Installation, Programming And Operating Instructions Download Page 40](http://html1.mh-extra.com/html/tyco/autopulse-z-10/autopulse-z-10_installation-programming-and-operating-instructions_1185685040.webp)
3-8
Special Purpose Monitor (SPM) circuits are used for connecting abort and manual release switches
to the AutoPulse Z-10. For all applications, the maximum voltage (open circuit) is 28 VDC, and
the maximum current is 75mA.
Note:
In Preaction/ Deluge applications SPMs are used for Waterflow and Supervisory switches. In
combination Agent Release and Preaction/Deluge (Applications 10 and 11) SPM1 is used for Abort/Manual and
SPM2 is used with a pressure switch. Please refer to Table 1-3 for details.
The application type (i.e., single hazard or dual hazard) determines the function of each SPM, as
follows. The chart below refers to applications 1-4 only.
Application
SPM Circuit Function
Single Hazard, Class A/B
SPM 1: Connect only abort switches.
SPM 2: Connect only manual release switches.
Refer to “Wiring Class A/B SPM Circuits for Single Hazard
Applications”.
Dual Hazard, Class A/B
Abort switches and manual release stations can share
SPM 1 and SPM2. An activated abort switch creates a current
limited state on the circuit, whereas a manual release station
creates a short on the circuit.
Refer to “Wiring Class B SPM Circuits for Dual Hazard
Applications” below.
Adhere to
Figure 3-5
and the following guidelines when wiring Special Purpose Monitor (SPM) for
a single hazard application. Connect abort switches to SPM1 and manual release stations to
SPM2. Do not combine abort switches and manual release stations on the same circuit. In
Preaction/ Deluge applications, SPM 1 is connected to Supervisory switches and SPM 2 to
Waterflow controls. As noted earlier, in combination Agent Release and Preaction/Deluge
(Applications 10 and 11) SPM1 is used for Abort/Manual and SPM2 is used with a pressure
switch.
Use only manual release switches that are UL-listed for fire use.
Use abort switch 433940 (flush mount).
Both manual release stations and abort switches must be normally open.
All wiring must be 12 AWG (max.) to 18 AWG (min.).
Conductors must test free of all grounds.
All wiring is supervised and power limited.
Leave 3.3 K, 1/2 W resistor across all unused SPM terminals.
Terminate Style B (Class B) circuits with a listed 3.3K, 1W (Part No. 431210) end-of-line
resistor.
For Canadian applications, attach the following resistor to a ULC-listed EOL device.
Part No. 431210 3.3K, 1W resistor
Terminate Style D (Class A) circuits at the Class A Adapter with a listed 3.3K, 1 W (Part No.
431210) end-of-line resistor. See
Figure 3-5
.
Maximum line resistance is 50 Ohms.
Normal condition (no devices closed). Current at 24 VDC: 6.0 mA
Manual Release condition. Current at 24 VDC: 25 mA
SPM Circuits do not support the connection of smoke or heat detectors.
When SPM wiring is routed outside the building, use Listed Secondary Protector 430685. A
protector must be installed at the building entrance such that protected wiring is segregated
from unprotected (outdoor) wiring.
Continued on next page
Wiring Special Purpose Monitor Circuits
Overview
Wiring Class A/B
SPM Circuits for
Single Hazard
Applications
Summary of Contents for AutoPulse Z-10
Page 1: ...Doc No 430545 Part No 579 357 Rev U 0579357T ...
Page 2: ...Blank Page Back of Front Cover ...
Page 6: ...vi ...
Page 32: ......