The manual releasing sequence begins following the activation of a manual release station
connected to the AutoPulse Z-10 FACP. As shown in
Figure 1-3
, the NACs and the Manual
Release Delay Timer turn on immediately after the switch is activated. Release of the agent
occurs immediately after the timer expires.
Note:
The abort switch has no effect on the manual release sequence.
In applications 10 and 11, Pre-action RAC2 turns on immediately.
Figure 1-3. Releasing Sequence Manual Station
Manual Release
Delay Timer*
0-30 Seconds
NAC1 On Steady
NAC2 120 BPM
Activate Alarm Relay
Sound Panel Piezo
Discharge Signals
NAC1 On Steady
NAC2 On Steady
RAC Activation (Agent Discharge)
M
anu
al
Switch
A
ctiv
atio
n
Al
ar
m
S
ilence
Al
ar
m
Re
set
*If timer is set to 0, release of the agent and
activation of the discharge signals occurs
immediately after activation of manual release
switch.
Supported Applications,
Continued
Releasing
Sequence for
Manual Release