1-5
Table 1-2 All 13 Applications With Enhanced Relay Operation
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1
SPM2
NAC1
NAC2
RAC1
RAC2
Timers
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Notes 1, 2, & 3
Note 4
Notes 4
& 5
Notes 9 & 10
Abort
Rel. Aux1
Aux2
Aux3
Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
1. Agent Release, Single Hazard, Cross-Zoned, Combined Release
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady Optional
Opt
TBL Alarm
Supv or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
Steady
120bpm
Opt
Start
Stage 3 - Release
Alarm
Steady
Steady
ON
ON
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
2. Agent Release, Single Hazard, Combined Release
Stage 1 - Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady 120bpm
Opt
Start
TBL Alarm
Supv or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
Stage 2 - Release
Alarm
Steady
Steady
ON
ON
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
3. Agent Release, Dual Hazard, Cross-Zoned
Hazard 1, Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Optional
Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Pre-
Discharge
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Pre-
Discharge
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
120bpm
Opt
Start
Hazard 1, Stage 3 - Release
Alarm
Steady
ON
Expired
Hazard 2, Stage 1 - 1st Alarm
IDC 3 or 4 Alarm
Abort MS
Optional
Opt
Hazard 2, Stage 2 - Alarm Confirmed
IDC 3 & 4 Alarm
120bpm
Opt
Start
Hazard 2, Stage 3 - Release
Alarm
Steady ON Expired
4. Agent Release, Dual Hazard
Hazard 1, Stage 1 - Alarm
IDC 1 or 2 Alarm
Abort
MS
120bpm
Opt
Start
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Pre-
Discharge
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Pre-
Discharge
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Release
Alarm
Steady
ON
Expired
Hazard 2, Stage 1 - Alarm
IDC 3 or 4 Alarm
Abort
MS
120bpm
Opt
Start
Hazard 2, Stage 2 - Release
Alarm
Steady
ON
Expired
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1 SPM2
NAC1
NAC2
RAC1
RAC2
Time-Limit
Cutout
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Note 6
Aux1
Aux2
Aux3
Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
5. Preaction/Deluge, Single Hazard, Cross-Zoned
Stage 1 - 1st Alarm
1st IDC in Alarm
Steady
Optional
Opt
TBL Alarm
Supv. or
Waterflow
(select.)
TBL Alarm
Waterflow
Discharge TBL Alarm
Waterflow
Discharge
Stage 2 - Alarm Confirmed / Release
2nd IDC in Alarm
Steady
Steady
ON
ON
Opt
Waterflow Alarm
WF
Steady
Steady
Note 7
Note 7
Supervisory Alert
Supv
Optional
6. Preaction/Deluge, Single Hazard, Combined Release
Releasing Alarm
Any 1 or more IDC's in Alarm
Steady
ON
ON
Opt
TBL Alarm
Supv. or
Waterflow
(select.)
TBL Alarm
Waterflow
Discharge TBL Alarm
Waterflow
Discharge
Waterflow Alarm
WF
Steady
Note 7
Note 7
Supervisory Alert
Supv
Optional
7. Preaction/Deluge, Dual Hazard, Cross-Zoned
Hazard 1, Stage 1 - Alarm
IDC 1 or 2 Alarm
Optional
Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Waterflow
Hazard 1
or Hazard
2
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Supv
Hazard 1
or 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Release
IDC 1 & 2 Alarm
Steady
ON
Opt
Hazard 2, Stage 1 - Alarm
IDC 3 or 4 Alarm
Optional
Opt
Hazard 2, Stage 2 - Release
IDC 3 & 4 Alarm
Steady
ON
Opt
Waterflow Alarm (both hazards)
WF
Steady
Steady
Note 7
Note 7
Supervisory Alert (both hazards, no NAC)
Supv
8. Preaction/Deluge, Dual Hazard
Hazard 1 - Releasing Alarm
IDC 1 or 2 Alarm
Steady
ON
Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Waterflow
Hazard 1
or Hazard
2
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Sups
Hazard 1
or 2
Discharge
Hazard 2
Hazard 2 - Releasing Alarm
IDC 3 or 4 Alarm
Steady
ON
Opt
Waterflow Alarm (both hazards)
WF
Steady
Steady
Note 7
Note 7
Supervisory Alert (both hazards, no NAC)
Supv
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1
SPM2
NAC1
NAC2
RAC1
NAC3
Timers
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Note 8
Abort
Rel. Aux1
Aux2
Aux3
Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
9. Agent Release, Single Hazard, Cross-Zoned, NYC abort
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady
Opt
TBL Alarm
Supv. or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
OFF
120bpm
Steady
Opt
Start
Abort switch pressed
Alarm
Steady
OFF
OFF
Opt
Suspend
Abort switch released
Alarm
Steady
OFF
OFF
Start
Investigate (Abort) Timer expired
Alarm
OFF
120bpm
Steady
Expired
Reload
Stage 3 - Release
Alarm
OFF
Steady
ON
Steady
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1
SPM2
NAC1
NAC2
RAC1
RAC2
Timers
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Agent
Release
Pre-
Action
Abort Rel. Aux1
Aux2
Aux3
Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
Agent
Release
Preaction/Deluge
10. Agent Release and Preaction/Deluge, Single Hazard, Cross-Zoned
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady
Optional
Opt
TBL Alarm
Supv. or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Waterflow
Discharge/
Pressure
Switch
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
Steady
120bpm
ON
Opt
Start
Stage 3 - Release
Alarm
Steady
Steady
ON
ON Expired
Waterflow Alarm
WF
Steady
Steady
Pressure Switch Alarm
Pressure Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
11. Agent Release and Preaction/Deluge, Single Hazard,
Stage 1 - Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady
Optional
ON
Opt
Start
TBL Alarm
Supv. or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Waterflow
Discharge/
Pressure
Switch
Stage 2 - Release
Alarm
Steady
Steady
ON
ON Expired
Pressure Switch Alarm
Pressure Steady
Steady
Waterflow Alarm
WF
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
Releasing Application
IDC 1
IDC 2
IDC 3
IDC 4
SPM1
SPM2
NAC1
NAC2
RAC1
NAC3
Timers
Panel Aux Relays
Relay Exp Board 1 (Hazard 1)
Relay Exp Board 2 (Hazard 2)
Strobe
Horn Bell
Abort
Rel.
Aux1
Aux2
Aux3
Relay 1
Relay 2
Relay 3
Relay 4
Relay 1
Relay 2
Relay 3
Relay 4
12. Agent Release, Single Hazard, Cross-Zoned, Bell/Horn/Strobe
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady
Opt
TBL Alarm
Supv. or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm
OFF
Optional
Opt
Start
Stage 3 - Release
Alarm
Steady
Steady
ON
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
13. Agent Release, Single Hazard, Bell/Horn/Strobe
Stage 1 - Alarm
IDC 1 or 2 Alarm
Abort
MS
Optional Steady
Opt Start
TBL Alarm
Supv. or
Pre-
Discharge
(select.)
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
TBL Alarm
Pre-
Discharge
Discharge/
Pressure
Switch
Stage 2 - Release
Alarm
Steady
Steady
ON
Expired
Pressure Switch Alarm
Pressure
Steady
Steady
Tamper Switch (Supervisory)
Supv.
Optional
Summary of Contents for AutoPulse Z-10
Page 1: ...Doc No 430545 Part No 579 357 Rev U 0579357T ...
Page 2: ...Blank Page Back of Front Cover ...
Page 6: ...vi ...
Page 32: ......