3-3
Any combination of the detectors and bases listed below may be installed, except only one
Part No. 430569 may be used per circuit. The compatibility identifier is the model number
found on the detector, base, and control unit. Compatible device Part Numbers are as follows:
(Refer to installation instructions 431424)
430559, Photoelectric Smoke (2.8 %) Detector
430560, Combination Photoelectric/Heat Detector
430561, Ionization Smoke Detector
430562, Photoelectric Smoke (3.5%) Detector
430565, 135
˚
Fixed Temperature with Rate-of-Rise Electronic Heat Detector
430566, 200
˚
Fixed Temperature with Rate-of-Rise Electronic Heat Detector
Compatible Bases. (Refer to Part No. 431425 for installation instructions.)
430567, Two Wire Base (30 / Loop)
430569, Two Wire Base with Aux. Alarm Relay (1 / Loop)
430570, Two Wire Base with LED (Part Nos. 430563 through 430566 only)
Wiring Initiating Device Circuits,
Continued
Guidelines
Summary of Contents for AutoPulse Z-10