![Twilight MC-SUP2000H Manual Download Page 29](http://html.mh-extra.com/html/twilight/mc-sup2000h/mc-sup2000h_manual_1183912029.webp)
Chapter 3 Menu Windows Arrangement
- 24 -
seconds the backlight will be on with every key pressing.
M71
LCD contrast control. The LCD will become darker when a small value is
entered.
M72
Working timer. It can be cleared by pressing ENT key, and then select
YES.
M73
Enter Lower Flow Rate value that will trigger the #1 Alarm. There are two
virtual alarms in the system. By “virtual” we mean that the user must
redirect the output of the alarms by setuping the output hardware in M78
and M77
M74
Enter the higher flow rate value that will trigger the #1 Alarm.
M75
Enter the lower flow rate value that will trigger the #2 Alarm.
M76
Enter the higher flow rate value that will trigger the #2 Alarm.
M77
Buzzer setup.
If a proper input source is selected, the buzzer will beep when the trigger
event occurs
M78
OCT (Open Collect Transistor Output) setup
By selecting a proper input source, the OCT hardware will close when the
trigger event occurs
M79
Set relay output options
M80
Select the quantitative (batch) controller to control the signal
M81
Select a quantitative (batch) controller
M82
Date totalizer
M83
Automatic supplementary power off flow switch
M84
Not used
M85
Not used
M86
Not used
M87
Not used
M88
Not used
M89
Not used
M90
Display signal strength, signal quality, time ratio on the upper right corner.
M91
Displays the Time Ratio between the Measured Total Transit Time and the
Calculated time. If the pipe parameters are entered correctly and the
transducers are properly installed, the ratio value should be in the range of
100±3%. Otherwise the entered parameters and the transducer installation
should be checked.
Displays the estimated fluid sound velocity. If this value has an obvious
Summary of Contents for MC-SUP2000H
Page 1: ...Medidor de flujo ultrasónico en líquidos portátil Meacon MC SUP2000H ...
Page 5: ......
Page 11: ...Chapter 1 Introduction 6 1 6 Parts Identification 1 6 1 Converter Front view Side view ...
Page 16: ...Chapter 1 Introduction 11 View and size Small size HS Medium size HM ...
Page 17: ...Chapter 1 Introduction 12 High temp Small size HS HT ...
Page 18: ...Chapter 1 Introduction 13 High temp Medium size HM HT Extension bracket ...
Page 69: ......