V01.01 | 2018/11
29
14
Technical Data
Technical Data
Power supply
Operating/load voltage
24 VDC
Permissible range
18…30 VDC
Operating current
From V1: < 100 mA
From V2: < 85 mA
Total current
Max. 4 A per voltage group,
V1 + V2: max. 5.4 A
Sensor/actuator supply VAUX1
Supply connector C0…C3 from V1 short-circuit proof,
120 mA per connector, with diagnostics
Sensor/actuator supply VAUX2
Supply connector C4…C7 from V2 short-circuit proof,
120 mA per connector, with diagnostics
Potential isolation
Galvanic isolation from V1 and V2 voltage group, voltages
up to 500 VDC
Inputs
Number of channels
16 digital pnp inputs (EN 61131-2)
Type of input diagnostics
Type of input diagnostics
Signal voltage, low level
-3…5 VDC (EN 61131-2, type 1 and 3)
Signal voltage, high level
11…30 VDC (EN 61131-2, type 1 and 3)
Input delay
2.5 ms
Max. input current
15 mA
Outputs
Number of channels
16 digital pnp outputs
Type of output diagnostics
Channel diagnostics
Output voltage
24 VDC from supply voltage
Output current per channel
1.8 A, short-circuit-proof
Output delay
1.3 ms
Load type
Ohmic, inductive lamp load
IO-Link
IO-Link specification
Specified according to version 1.1
Parameterization
FDT/DTM, IODD
Transmission rate
COM 2: 38,4 kbit/s
Transmission physics
3-wire physics (PHY2)
Minimum cycle time
4.2 ms
Connectors
IO-Link
M12 × 1, 5-pole
Input/output
M12 × 1, 5-pole
Permissible torques
n
IO-Link
n
I/O channels
n
Mounting (M4 screws)
0.8 Nm
0.8 Nm
0.5 Nm