Parameterizing and Configuring
Parameters
18
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Pulse Stretching Input – 0×43 (67)
This parameter defines the duration of the pulse stretching for digital input edges in multiples
of 10 ms. This allows that even short signals with longer PLC cycle times can be detected.
Format
Length
Array of Bytes
8 byte
1 byte per channel
Default values are
shown in bold.
Value
Meaning
0
disabled
Pulse stretching deactivated
1
1…255
Pulse stretching input [*10 ms]
Bit offset
Bit offset
0
8
16
24
32
40
48
56
64
72
80
88
96
104
112
120
Sub index
Sub index
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.
Manual Output Reset after Overcurrent – 0x44 (68), Sub Index 0
This parameter defines if a manual reset is necessary after an overcurrent occurred at the digital
channel.
Format
Length
Byte
1 byte
1 bit per channel
Default values are
shown in bold.
Value
Meaning
0
No
Automatic recovery mode
1
Yes
Controlled recovery mode (output has to be reset manually)
Byte 0
Byte 1
Bit offset
Bit offset
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.