Operating
Evaluating Diagnostic Data
24
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.4
Evaluating Diagnostic Data
Group Diagnostics: Undervoltage V1/V2 and Overcurrent Sensor Supply – 0x50 (80), Sub
Index 0
Indicates errors in the module and sensor supply:
n
Group diagnostics: Diagnostics pending at the module
n
Undervoltage V1 (per module)
n
Undervoltage V2 (per module)
n
Overcurrent sensor supply (per connector)
Format
Length
Array of Bytes
2 byte
0 = no diagnostics
1 = diagnostic message
Byte 0
Bit offset
15
14
13
12
11
10
9
8
Group diagnostics -
-
-
Undervoltage
supply V2
Undervoltage
supply V1
-
-
Byte 1
Bit offset
7
6
5
4
3
2
1
0
Overcur-
rent Vsens
C7
Overcur-
rent Vsens
C6
Overcur-
rent Vsens
C5
Overcur-
rent Vsens
C4
Overcur-
rent Vsens
C3
Overcur-
rent Vsens
C2
Overcur-
rent Vsens
C1
Overcur-
rent Vsens
C0