Parameterizing and Configuring
Parameters
20
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Enable Undervoltage Diagnosis V2/Undervoltage Value for V1 and V2 – 0×46 (70), Sub Index
0
This parameter defines whether undervoltage diagnostics are sent to in case of an V2 under-
voltage. Additionally it defines the threshold values for undervoltage diagnostics for V1 and V2.
Format
Length
Array of Bytes
2 byte
2 bit per module
The default values are written in
bold
.
Value
Meaning
Activate V2 diagnostics
0
No
1
Yes
V2 diagnostics activated
Threshold value for undervoltage diagnostics V1 and V2
0
Standard
(IEC 61131-2)
lower threshold: 19.2 V
upper threshold: 20.4 V
1
Extended
lower threshold: 17.5 V
Byte 0
Bit offset
7
6
5
4
3
2
1
0
-
-
-
-
-
-
Activate diagnostics
Threshold
Byte 1
Bit offset
7
6
5
4
3
2
1
0
-
-
-
-
-
-
-
-