Output After Error – 0x45 (69), Sub Index 0
This parameter defines the behavior of the output in case of an interruption of the IO-Link com-
munication.
Format
Length
Array of Bytes
2 byte
2 bit per channel
Default values are
shown in bold.
Value
Meaning
00
0
Set output to 0
01
1
Set output to 1
10
Current value
Hold current value
11
reserved
Byte 3
Byte 2
Byte 1
Byte 0
Bit offset
Bit offset
Bit offset
Bit offset
6
4
2
0
6
4
2
0
6
4
2
0
6
4
2
0
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.