Operating
IO-Link Error Codes
26
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.5
IO-Link Events
Event
Code
Description
Event Mode
0x5111 Undervoltage
supply V1
0xF4 (appears)
Undervoltage at the
supply group V1 (C0…C3)
0xB4 (disappears)
0x5112 Undervoltage
supply V2
0xF4 (appears)
Undervoltage at the
supply group V2 (C4…C7, Class B supply)
0xB4 (disappears)
0x7710 Overcurrent Vsens
connector x
or
overcurrent output x
0xF4 (appears)
Group event for overcurrent:
Overcurrent of the sensor supply at one of
the connectors (C0…C7)
or
overcurrent at one of the outputs
(DO0…DO15)
The mapped diagnostics in the process
image of the inputs show which slot or
output detects an overcurrent.
0xB4 (disappears)
9.6
IO-Link Error Codes
Error code
Description
0x8011
Index not available
0x8012
Sub Index not available
0x8023
Accesss denied
Index cannot be written
0x8030
Parameter value out of range
Parameter value out of range
0x8033
Parameter length overrun
Length of data to be written does not
match the length defined for this para-
meter.
0x8034
Parameter length underrun
0x8035
Function not available
Function not available in the device
0x8041
Inconsistent parameter set
Inconsistent parameters