Parameterizing and Configuring
Parameters
16
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
ISDU
Index
Hex.
(Dec.)
Object name
Access
Length
[Byte]
Meaning/
default value
Comment
0x1A
(26)
Location Tag
read/
write
32
Default "***"
The application-spe-
cific installation loca-
tion of the device can
be stored in this field.
IO-Link object directory – ISDU device parameters: Preferred Index (parameters and
diagnostics of the digital in- and outputs)
ISDU
Index
Hex.
(dec.)
Object name
Access
Length
[Byte]
Meaning
0x40
(64)
Parameter ID
read/
write
4
Customer-specific ID, for free use
0x41
(65)
Inverting
Input
read/
write
2
Invert digital input
0x42
(66)
Activate
Output
read/
write
2
Activate output
0x43
(67)
Impulse
Stretching
Input
read/
write
16
Pulse stretching input
0x44
(68)
Short Circuit
Recovery
read/
write
2
Manual output reset after overcurrent
0x45
(69)
Failsafe
read/
write
4
Output After Error
0x46
(70)
Under
Voltage
Diagnostics
read/
write
2
Enable undervoltage diagnosis V2/Under-
voltage value for V1 and V2
Diagnostics
0x50
(80)
Supply Error
read
only
2
n
Undervoltage supply V1/V2
n
Overcurrent Vsens Connector C0…C7
0x51
(81)
Output Short
Circuit
read
only
2
Overcurrent output 0…15