Application example: FGEN for EtherNet/IP™ with Allen Bradley PLC and RS Logix 5000
D301271 1013 - FGEN - multi protocol
8-6
4
In the Assembly Instances 103 and 104, please enter the connection parameters of the station.
5
In the "Connection" tab set the "Requested Packet Interval" (RPI) to 10 ms, which normally should
be the default setting. For FGEN, the RPI should be set to 5 ms or higher.
6
Configuration of FGEN-IOM-5001
Figure 8-8:
Configuration
of FGEN-IOM-
5001
Note
If the variable Assembly Instances 103 and 104 (see
) are used, the Connection
Parameters have to be set according to the actual station configuration which means, the in-
and output sizes have to match the sizes definitely required by the station. This required in-
and output size can be read out using Assembly Class (0×04), instance 0×67, attr. 0×04 and
Assembly Class (0×04), instance 0×68, attr. 0×04.
Figure 8-9:
Set connection
options for
FGEN
Figure 8-10:
Configuration
of FGEN-IOM-
5001