Application example FGEN for Modbus TCP with CODESYS Win V3
D301271 1013 - FGEN - multi protocol
10-26
10.3.12 Evaluation of the status word of FGEN-XSG16-5001 (%IW1)
According to the definition of the Modbus communication channel (see
, example 4,
), %IW1 contains station's the status-word.
the message is to be interpreted as follows:
%IW 2, "actual value" = 129
1
Byte 0, bit 0 = 1
→
status message: „DiagWarn“ = active diagnosis
2
Byte 0, bit 7 = 1
→
status message: „U
L
“ = load voltage not within the permissible range (< 18 V).
register
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0×0001
U
L
-
-
-
-
-
-
Diag
Warn
-
FCE -
-
CFG
COM
U
B
-
Figure 10-27:
Status word of
the station