Implementation of EtherNet/IP™
D301271 1013 - FGEN - multi protocol
7-4
7.2
QC - QuickConnect
7.2.1
General
QuickConnect enables a PLC to build up connections to EtherNet/IP™-nodes in less than 300 ms after
switching-on the power supply for the EtherNet/IP™-network. This fast start up of devices is above all
necessary for robotic tool changes for example in the automobile industry.
7.2.2
QuickConnect in FGEN
TURCK FGEN-stations support QuickConnect.
QuickConnect is activated:
via the configuration data in the PLC-program per
Assembly Class 0×04, Configuration Assembly 106, bit 9 = 1
(see also
Activating QuickConnect (page 8-13)
or
via Class Instance Attribute in
TCP/IP Interface Object (0×F5), instance 1, attribute 12 (0×C0)
Note
For correct cabling with FGEN in QC-applications, see
Ethernet-connection in QC-/FSU-
Note
Activating the QuickConnect-function leads to the automatical setting of all necessary port-
properties:
Autonegotiation
transmission speed
Duplex
Topology
AutoMDIX
= deactivated
= 100BaseT
= full duplex
= linear
= deactivated
Summary of Contents for FGEN-AIM Series
Page 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Page 8: ...D301271 1013 FGEN multi protocol vi...
Page 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Page 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Page 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Page 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Page 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...