D301271 1013 - FGEN - multi protocol
9-9
Modbus registers
The following table shows the register mapping for the different Modbus addressing methods
Table 9-4:
Mapping of
Modbus regis-
ters (holding
registers)
Description
Hex
Decimal
5-digit
Modicon
packed input data
0×0000
to
0×01FF
0
to
511
40001
to
40512
400001
to
400512
packed output data
0×0800
to
0×09FF
2048
to
2549
42049
to
42560
402049
to
402560
Station Identifier
0×1000
to
0×1006
4096
to
4102
44097
to
44103
404097
to
404103
Station status
0×100C
4108
44109
404109
process image length in bit for the
intelligent output modules
0x1010
4112
44113
404113
process image length in bit for the
intelligent input modules
0x1011
4113
44114
404114
process image length in bit for the digital
output modules
0x1012
4114
44115
404115
process image length in bit for the digital
input modules
0x1013
4115
44116
404116
watchdog, actual time
0x1020
4128
44129
404129
watchdog, predefined time
0x1120
4384
44385
404385
Modbus connection mode register
0x1130
4400
44401
404401
Modbus connection timeout in sec.
0x1131
4401
44402
404402
Modbus parameter restore
0x113C to
0x113D
4412 to
4413
44413 to
44414
404413 to
404414
Modbus parameter save
0x113E to
0x113F
4414 to
4415
44415 to
44416
404415 to
404416
deactivate protocol
0x1140
4416
44417
404417
active protocol
0x1141
4417
44418
404418
System voltage U
SYS
[mV]
0x2400
9216
49217
409217
Load voltage U
L
[mV]
0x2401
9217
49218
409218
process data inputs
(max. 2 registers per station)
0×8000,
0×8001
32768
32769
-
432769
432770
process data outputs
(max. 2 registers per station)
0×9000,
0×9001
36864,
36865
-
436865,
436866
Summary of Contents for FGEN-AIM Series
Page 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Page 8: ...D301271 1013 FGEN multi protocol vi...
Page 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Page 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Page 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Page 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Page 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...