![turck FGEN-AIM Series User Manual Download Page 183](http://html1.mh-extra.com/html/turck/fgen-aim-series/fgen-aim-series_user-manual_1181725183.webp)
D301271 1013 - FGEN - multi protocol
13-5
Electromagnetic compatibility(EMC
13.3
Electromagnetic compatibility(EMC
The TURCK products comply in full with the requirements pertaining to EMC regulations. Nevertheless,
an EMC plan should be made before installation.
Hereby, all potential electromechanical sources of interference should be considered such as galvanic,
inductive and capacitive couplings as well as radiation couplings.
13.3.1
Ensuring electromagnetic compatibility
The EMC of the stations is guaranteed when the following basic rules are adhered to:
Correct and large surface grounding of inactive metal components.
Correct shielding of cables and devices. The grounding lug at the Ethernet-connectors has to be
connected as low-impedance as possible to earth.
Proper cable routing – correct wiring.
Creation of a standard reference potential and grounding of all electrically operated devices.
Special EMC measures for special applications.
13.3.2
Grounding of inactive metal components
All inactive metal components (for example: switchgear cabinets, switchgear cabinet doors, supporting
bars, mounting plates, tophat rails, etc.) must be connected to one another over a large surface area
and with a low impedance (grounding). This guarantees a standardized reference potential area for all
control elements and reduces the influence of coupled disturbances.
In the areas of screw connections, the painted, anodized or isolated metal components must be
freed of the isolating layer. Protect the points of contact against rust.
Connect all free moving groundable components (cabinet doors, separate mounting plates, etc.) by
using short bonding straps to large surface areas.
Avoid the use of aluminum components, as its quick oxidizing properties make it unsuitable for
grounding.
13.3.3
PE connection
A central connection must be established between ground and PE connection (protective earth).
Warning
The grounding must never – including cases of error – take on a dangerous touch
potential. For this reason, always protect the ground potential with a protective cable.
Summary of Contents for FGEN-AIM Series
Page 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Page 8: ...D301271 1013 FGEN multi protocol vi...
Page 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Page 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Page 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Page 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Page 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...