FGEN – general technical properties
D301271 1013 - FGEN - multi protocol
3-22
3.9
Status and Control Word of the FGEN-stations
The Status as well as the Control Word are mapped into the station's process data.
EtherNet/IP™
In EtherNet/IP™, the mapping can be disabled, see
,
and
GW Control Register (page 7-30)
Modbus TCP
→
Register 100Ch: "Station status" (page 9-16)
PROFINET
→
PROFINET-Error Codes (page 11-4)
3.9.1
Status Word
Meaning of the status bits
3.9.2
Control Word
The Control Word has no function at the moment, it is reserves for further use.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Status
0
U
L
-
-
-
-
-
-
Diag
Warn
1
-
FCE
-
-
CFG
COM
U
B
-
Table 3-3:
Meaning of the
status bits
Name
Meaning
DiagWarn
Summarized diagnosis of the device. At least 1 channel sends diagnostics.
U
L
Load voltage not within the permissible range (18 to 30 V)
U
B
System voltage not within the permissible range (18 to 30 V)
COM
I/O Communication Lost Error
No Communication on the module bus.
CFG
I/O CfgModified Error
The I/O-configuration has be changed and is no longer compatible.
FCE
Force Mode Active Error
The Force Mode is activated, which means, the actual output values may no match the
ones defined and sent by the field bus.
Summary of Contents for FGEN-AIM Series
Page 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Page 8: ...D301271 1013 FGEN multi protocol vi...
Page 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Page 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Page 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Page 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Page 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...