D301271 1013 - FGEN - multi protocol
13-7
Potential compensation
13.5
Potential compensation
Potential differences can occur between installation components that are in separate areas if these
are fed by different supplies,
have double-sided conductor shields which are grounded on different installation components.
A potential-compensation cable must be routed to the potential compensation.
A potential compensation cable must have the following characteristics:
Low impedance. In the case of compensation cables that are routed on both sides, the
compensation line impedance must be considerably smaller than that of the shield connection
(max. 10% of shield connection impedance).
Should the length of the compensation cable be less than 200 m, then its cross-section must be at
least 16 mm
2
/0.025 inch
2
. If the cable length is greater than 200 m, then a cross-section of at least
25 mm
2
/ 0.039 inch
2
is required.
The compensation cable must be made of copper or zinc coated steel.
The compensation cable must be connected to the protective conductor over a large surface area
and must be protected against corrosion.
Compensation cables and data cables should be routed as close together as possible, meaning the
enclosed area should be kept as small as possible.
13.5.1
Switching inductive loads
In the case of inductive loads, a protective circuit on the load is recommended.
13.5.2
Protection against Electrostatic Discharge (ESD)
Warning
Never use the shield as a potential compensation.
Figure 13-2:
potential
compensation
Attention
Electronic modules and base modules are at risk from electrostatic discharge when
disassembled. Avoid touching the bus connections with bare fingers as this can lead to
ESD damage.
Reference potential
Potential compensation cable
Shield
Reference potential
Summary of Contents for FGEN-AIM Series
Page 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Page 8: ...D301271 1013 FGEN multi protocol vi...
Page 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Page 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Page 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Page 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Page 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...