![turck FGEN-AIM Series User Manual Download Page 84](http://html1.mh-extra.com/html/turck/fgen-aim-series/fgen-aim-series_user-manual_1181725084.webp)
Implementation of EtherNet/IP™
D301271 1013 - FGEN - multi protocol
7-30
Object Instance 2
Table 7-24:
Object Instance 2,
Gateway Instance
Attr. No.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
109
(6Dh)
Status register 2
G
STRUCT
The Status Word contains general station
status information:
Station
– Bit 15: reserved
– Bit 14: "Force Mode Active Error" The Force
Mode is activated.
– Bit 13: reserved
– Bit 12: reserved
Internal bus
– Bit 11 "I/O Cfg Modified Error"
The configuration has been changed in an
incompatible way.
– Bit 10 "I/O Communication Lost Error"
Communication on the internal module bus
disturbed.
Voltage errors
– Bit 09 "U
sys
too low" System voltage too low
(< 18 VDC).
– Bit 08: reserved
– Bit 07: "U
L
too low" Load voltage too low (< 18
VDC).
– Bit 06: reserved
– Bit 05: reserved
– Bit 04: reserved
Warnings
– Bit 03: reserved
– Bit 02: reserved
– Bit 01: reserved
– Bit 00: "I/O Diags Active Warning" At least one
I/O-channel sends active diagnostics.
115
(73h)
ON IO
CONNECTION
TIMEOUT
G/S
ENUM
USINT
Reaction to the I/O connection exceeding the
time limit.
SWITCH IO FAULTED (0):
The modules are switched to Faulted State.
SWITCH IO OFF (1):
The gateway switches off the outputs of the
modules.
SWITCH IO HOLD (2):
No further changes to the I/O-data. The
outputs are held.
138
(0×8A)
GW Status
register
Get/
Set
DWORD
Allows to enable/disable the status register
which is part of the input data.
139
(0×8B)
GW Control
Register
Get/
Set
DWORD
Allows to enable/disable the control register
which is part of the output data.
Summary of Contents for FGEN-AIM Series
Page 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Page 8: ...D301271 1013 FGEN multi protocol vi...
Page 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Page 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Page 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Page 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Page 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...