9
2018/03
Protocol properties
Modbus TCP
Address assignment
Static IP (rotary coding switches), BOOTP, DHCP
Supported Function Codes
FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Number of connections
8
Input data size
Max. 240 registers
Register start address
12288 (0x3000)
Output data size
Max. 240 registers
Output register start address
13312 (0x3400)
EtherNet/IP™
Address assignment
According to EtherNet/IP™ standard
Number of connections
3
PROFINET
Address assignment
DCP
Conformance class
B (RT)
MinCycleTime
1 ms
Fast Start-Up (FSU)
< 150 ms
Diagnostics
According to PROFINET Alarm Handling
Topology detection
Supported
Automatic address assignment
Supported
Inputs
Number of channels
16
Connection technology inputs
M12, 5-pole
Input type
PNP
Type of input diagnostics
Group diagnostics
Switching threshold
EN 61131-2 type 3, PNP
Low level signal voltage
< 5 V
High-level signal voltage
> 11 V
Low-level signal current
< 1.5 mA
High-level signal current
> 2 mA
Input delay
2.5 ms
Electrical isolation
Galvanic isolation to P1/P2, voltage proof up to 500
VDC
Tests
Vibration test
According to EN 60068-2-6/ IEC 68-2-47,
Acceleration up to 20 g
Drop and topple
According to IEC 60068-2-31/IEC 60068-2-32 1
Shock test
According to EN 60068-2-27
EMC
According to EN 61131-2
Ambient conditions
Temperature range
– Operating temperature
- 40 °C…+ 70 °C
– Storage/transport
- 40 °C…+ 85 °C