21
2018/03
5.2
Address Setting at FEN20-EN1
The FEN20-EN1 is permanently set to mode PGM-DHCP. A factory reset (F_Restet) can be performed
by pressing the “Reset” button that is recessed into the front of the device.
5.3
Assign the IP Address with Turck Service Tool (Port 1 only)
The Turck Service Tool can be used to set the IP address of either the TBEN-Lx-EN1 or the FEN20-EN1
in rotary switch mode PGM (500) or PGM_DHCP (600). The tool can also be used to change the first
3 octets of the IP address as well as netmask and gateway in other rotary switch modes.
Open Turck Service Tool and click “Search”.
Click on the device to be addressed and change the IP configuration via “Change”.
NOTE
For the TBEN-Lx-EN1 and the FEN20-EN1 Ethernet spanner modules the Ethernet cable
must be plugged into port 1 for the Turck Service Tool to work correctly. The address of
port 2 can not be set with Turck Service Tool. If the IP addresses for both ports need to be
assigned, the web server or PROFINET DCP is recommended and discussed in the follow-
ing section.
Fig. 13: Turck Service Tool – found devices