13
2018/03
4
Connecting
4.1
Connecting TBEN-L…-EN1
Connecting the Device to Ethernet
For the connection to Ethernet, the device has an integrated autocrossing switch with two 4-pin
M12 Ethernet sockets. The maximum tightening torque is 0.6 Nm.
Connect the device to the field bus according to the pin assignment shown below.
Connecting the Power Supply
For the connection to the power supply and the feeding through of the power, the device has two
5-pin 7/8" connectors. The power supply connectors are designed as 4-pole (TBEN-L4) or 5-pole
(TBEN-L5) 7/8" connectors. V1 and V2 are galvanically isolated. The maximum tightening torque is
0.8 Nm.
Connect the device to the power supply according to the pin assignment shown below.
Fig. 3: M12 Ethernet sockets
Fig. 4: Pin assignment Ethernet connectors
Supply voltage 7/8“, 5-pole
Pin assignment
X1= voltage IN
X2 = voltage OUT for supplying the next node
V1 = supply voltage 1 (incl. supply of electronics)
V2 = supply voltage 2
v
4
1
3
2
P1, P2
1 = TX +
2 = RX +
3 = TX –
4 = RX –
flange = FE
1 BK = V2 (–)
2 BU = V1 (–)
3 GNYE = FE
4 BN = V1 (+)
5 WH = V2 (+)
3
4
5
2
1
w
v
3
4
5
2
1
X1
X2