➄
Temperature
You can change the setpoint temperature in incre-
ments of 1 K You can change the default setpoint
temperature from -3 K ... +3 K.
Example:
Default setpoint temperature: 21 °C
Minimum temperature you can set: 18 °C
Maximum temperature you can set: 24 °C
Increase of the setpoint temperature. (Room /
extract air or supply air temperature, depending
on the control strategy)
Reduction of the setpoint temperature. (Room /
extract air or supply air temperature, depending
on the control strategy)
The control strategy can be configured via the
settings.
➅
Ventilation
Automatic ventilation; the fan speed depends on the
controller.
Press or briefly to switch between the fan
stages.
Manual ventilation at the lowest speed (fan stage).
Manual ventilation control at a medium level.
Manual ventilation at the highest speed (fan stage).
Retreat - Operation with lowered airflow for quiet
working.
Boost - Operation with maximum airflow for quick
room flushing with fresh air.
Standby operation The ventilation units are
switched off.
No temperature maintenance.
Display of the activated fume cupboard switching (fan force)
The stage corresponds to the fan stage of the supply air (configurable).
Activation takes place via fume cupboard switching or via the BAS/MCD. When the fume cupboard
switching is active, operation via the control panel is not possible.
Operation
Control panel > Digital control panel
Decentralised ventilation units SCHOOLAIR-S-HV
37