Thermokon, without selector switch, Berker S.1/Q.3,
Busch Jäger Futura
X9
1
2
3
4
5
7
5
4
3
2
1
8
1
2
9
10
6
Fig. 30: Wiring of Thermokon control panel to terminal
X9
1
Control panel without selector switch, for flush
mounting, suitable for switches from the following
ranges:
Berker S.1:
Type WRF07 PTD NTC 20k BType6 5k gn,
TROX order no. A00000079778
Busch Jäger Futura:
Type WRF07 PTD NTC 20k BType6 5k gn,
TROX order no. A00000079779
Berker Q.3:
Type WRF07 PTD NTC 20k BType6 5k gn,
TROX order no. A00000081579
2
LiYCY 5 x 0.5 mm² shielded (by others)
Thermokon, without selector switch, without set-
point value adjuster, Gira E2
X9
1
2
3
4
5
5
4
3
2
1
9
1
2
11
12
10
Fig. 31: Wiring of Thermokon control panel to terminal
X9
1
Control panel without selector switch and without
setpoint value adjuster, for flush mounting, suitable
for Gira E2 switch range, type WRF06 TD NTC 20k,
TROX order no. A00000081503
2
LiYCY 5 x 0.5 mm² shielded (by others)
6.4.3 Connection of room temperature
sensor
X9
1
2
3
4
5
2
1
1
2
Fig. 32: Connection of room temperature sensor
1
Room temperature sensor, type RTF3-NTC10k,
TROX order no. A00000059069
2
LiYCY 2 x 0.5 mm² shielded (by others)
Installation
Making electrical connections > Connection of room temperature sensor
Decentralised ventilation units SCHOOLAIR-S-HV