Honeywell, 5-stage (0, 1, 2, 3, AUTO)
BYP / RTN 6
LED 5
BYP / FAN 4
SET PT 3
SENSOR 2
COM 1
LED / RTN 7
X9
1
2
3
4
5
1
2
Fig. 26: Wiring of Honeywell control panel, 5
‑
stage to
terminal X9
1
Control panel with selector switch, for surface
mounting, type: T7460F1000, TROX order no.
M546FB8
2
LiYCY 5 x 0.5 mm² shielded (by others)
Thermokon, with selector switch, 5-stage
X9
1
2
3
4
5
6
5
4
3
2
1
7
1
2
11
12
8
Fig. 27: Wiring of Thermokon control panel (5-stage) to
terminal X9
1
Control panel with selector switch, for surface
mounting, type WRF04 PSTD NTC20k 5k FS5 gn
5V SA, TROX order no. A00000082515
2
LiYCY 5 x 0.5 mm² shielded (by others)
Schneider, without selector switch
X9
1
2
3
4
5
21
LED RET 16
LED 5VDC 14
SET PT 13
SNSR/BUTTON/SETPT RT 12
SNSR/BUTTON 11
22
1
2
Fig. 28: Wiring of control panel STR 504 to terminal X9
1
Control panel without selector switch, for surface
mounting, type: STR 504 TROX order no. M536BA4
2
LiYCY 5 x 0.5 mm² shielded (by others)
Thermokon, without selector switch
X9
1
2
3
4
5
5
4
3
2
1
9
1
2
11
12
10
Fig. 29: Wiring of Thermokon control panel to terminal
X9
1
Control panel without selector switch for surface
mounting, type WRF04 PTD NTC 20k 5k gn, TROX
order no. A00000079777
2
LiYCY 5 x 0.5 mm² shielded (by others)
Installation
Making electrical connections > Connection of the control panel
Decentralised ventilation units SCHOOLAIR-S-HV
24