Veefil-RT 175-S Site Installation Manual
TRI125.INS.018 version 1
4 March 2020
Manual
Page 3 of 25
1
Overview
1.1
Purpose of this document
The purpose of this document is to provide qualified electrical engineers and Tritium
Certified installers with an outline of the steps required to install a Veefil-RT 175-S high
power charging 175kW site.
This document is for both the single and dual cable variants of the Veefil-RT 175-S.
Note:
The images used in this document are of the dual cable variant.
1.2
Disclaimer and warranty
This Manual sets out
Tritium’s understanding of best-practice methodologies and its
requirements for installation of the Veefil-RT 175-S and is provided to customers pursuant to
the same terms and conditions under which Tritium has supplied its products.
Tritium encourages all owners of its products to consult a qualified engineering consultancy
firm to provide independent advice on the methodologies set out in this manual, and site
design requirements, including in relation to applicable regulatory and statutory
requirements. All site designs must be signed off on by a professional engineer.
Tritium accepts no liability for any loss caused, whether due to negligence or otherwise
arising from the strict adherence to the requirements set out in this manual in contravention
of local regulatory and legal requirements.
It is an express condition of Tritium’s manufacturer warranty that:
•
the requirements set out in this manual are adhered to (subject to local regulatory and
legal requirements) when installing the Veefil-RT 175-S; and
•
that the installation is conducted by a Tritium Certified technician who has completed
Tritium’s installation training course for the Veefil-RT 175-S.
1.3
Specifications
Unit
Specifications
LV Distribution Board
•
185kVA Output per charger
•
400V/300A 50Hz, 480V/250A 60Hz, 600V/200A 60Hz
•
UL listed circuit breakers with optional under-voltage relay
•
Maximum available fault current of 18kA (current limiting fuses or
current limiting circuit breakers may be required to maintain limit
of 18kA)
•
Residual current monitoring device of time delay type (optional)
Power unit
•
1 x 185kVA double insulated safety isolation transformer
•
1 x 175kW AC/DC converter with AC contactors
•
Integrated Communications Unit, Dual 4G SIM
•
800kg
User unit
•
1 x 175kW 350A DC/DC converter (CCS/CHAdeMO)
•
260kg
1.4
Installation safety considerations
•
First Aid Kit
•
Low Voltage Rescue Kit (LVR Kit)
•
Defibrillator
•
Never walk under suspended loads