Veefil-RT 175-S Site Installation Manual
TRI125.INS.018 version 1
4 March 2020
Manual
Page 18 of 25
Strip, bootlace (only if stranded wire, skip bootlace if solid core), and insert the wires
into the field wiring terminals as follows:
Terminal
Wire
2
•
User Unit 230 VAC Neutral
7
•
User Unit 230 VAC Line
18
•
User Unit 24V Safety Loop
19
•
User Unit 24V Safety Loop
22
•
IMI Earth reference (from supply)
•
IMI Earth reference (to user unit)
11
•
(optional) upstream breaker shunt
output, 230 VAC Line
4
•
(optional) upstream breaker shunt
output 230, VAC Neutral
Locate the Ethernet cable from the control shelf and use the tool-less jack from the
installation kit to terminate the Cat6A cable.
Note:
Use colour code A for all Cat connections.
Cover the Ethernet jack in heat shrink and secure to the frame of the IPU.
Connect a 1m patch lead from the Ethernet jack to the control shelf.
Note:
Alternatively, terminate the cable directly with a male connector and insert this
into the control shelf.
Figure 13: Cat6A tool-less, Example Ethernet Terminations