WSP™
DATA SHEET
WSP™ SELF-PRIMER PUMPS
WSP-D300_8
Rev. 3
01/09/20
© 2019 The Factory
46
During low discharge head applications under 30-feet or 9-meters, Weir
Specialty Pumps advises a bypass line running back to the wet-well. Place
the bypass line at the cut-off point of the low-level pump or 6 inches below
the level of the water.
Occasionally, installations of the bypass line will end with a 6 to 8 foot length
of 1½-inch I.D.
smooth-bore
hose. In these cases, any air and liquid that is
vented during priming will vibrate the hose, breaking up remaining solids,
grease or other materials residing in the line. This reduces clogging.
BYPASS LINES MUST BE SECURED AGAINST BEING DRAWN INTO THE PUMP
SUCTION INLET WHEN RETURNED TO A WET WELL.
Weir Specialty Pumps advises the installation of pipe unions in a bypass line
at every 90º elbow to facilitate disassembling the parts for maintenance and
repair.
If the pump is used on high discharge head applications extending more than
30 feet under full working pressure, a larger volume of liquid may be
bypassed back to the wet-well. Such an occurrence will reduce the pumps
performance. To avoid this, Weir Specialty Pumps advises installing a
WSP™ ARV (WSP™ Automatic Air Release Valve) in the bypass line.
WSP™ ARVs offer low maintenance and high levels of dependability. For
more information, see the WSP™ ARV in this section for information on its
operation and installation. Contact your local WSP™ distributor or the factory
to select a WSP™ ARV that fits your application.
When installation of a WSP™ Self-Primer (WSP) Pump involves submerged
suction such as those in underground applications, Weir Specialty Pumps
advises installing a pipe union and manual shut-off valve in the bleed line.
This allows service staff to maintain the valve without being required to shut
down the station. This also minimizes any chance of flooding. A full opening,
ball-type valve that prevents solids from plugging the line must be used in
applications where a manual shut-off valve is located
anywhere
in the air
release piping.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN SEVERE INJURY.
WHEN A MANUAL SHUT-OFF VALVE IS INSTALLED IN A BYPASS LINE, IT MUST
REMAIN OPEN DURING OPERATION. CLOSING THE MANUAL SHUT-OFF VALVE
Summary of Contents for 8-WSP
Page 62: ...WSP DATA SHEET WSP SELF PRIMER PUMPS WSP D300_8 Rev 3 01 09 20 2019 The Factory 62 ...
Page 63: ...WSP DATA SHEET WSP SELF PRIMER PUMPS WSP D300_8 Rev 3 01 09 20 2019 The Factory 63 ...
Page 64: ...WSP DATA SHEET WSP SELF PRIMER PUMPS WSP D300_8 Rev 3 01 09 20 2019 The Factory 64 ...
Page 65: ...WSP DATA SHEET WSP SELF PRIMER PUMPS WSP D300_8 Rev 3 01 09 20 2019 The Factory 65 ...
Page 66: ...WSP DATA SHEET WSP SELF PRIMER PUMPS WSP D300_8 Rev 3 01 09 20 2019 The Factory 66 ...