www.trikdis.com
25
February, 2020
“Ethernet” communicator
E16
“Module” tabs
After adding the expander to the communicator as described above, in the
RS485 modules
window a new tab will appear with
this module’s settings. The tab will be given a number. Bellow we describe the settings for
iO-8
and
iO
series expanders.
iO-8 expander settings window
Expander
iO-8
has 8 universal (input/output) terminal contacts. Up to four
iO-8
expanders can be connected.
Input Count
– select what number of terminal contacts should be set to input (IN) mode. The rest of the terminal contacts
will become outputs (OUT).
Settings for controllable outputs are set directly in Protegus app. There you can assign an output for arming/disarming the alarm
system or for remote control of devices.
In the table inputs can be assigned Contact ID event and restore codes. After input is triggered, the communicator will send an
event with set event code to monitoring station receiver, Protegus app.
Contact ID event code:
Enable
– allow message transmission, when the input is triggered.
E/R
– choose what type of event will be sent when input is triggered –
Event
or
Restore
.
CID
– assign a Contact ID event code to the input.
Part.
– assign the partition (area) to the input. It is set automatically: if the module no. is 1, then the area is 91; if the
module no. is 4, then the area is 94.
Zone
– set the zone number for the input.
Contact ID restore code
:
Enable
– allow message transmission when the input is restored.
E/R
– choose what type of event will be sent when input is restored –
Restore
or
Event
.
CID
– assign the Contact ID restore code to the input.
Part.
– assign the partition (area) to the input. It is set automatically: if the module no. is 1, then the area is 91; if the
module no. is 4, then the area is 94.
Zone
– set the zone number for the input.
Input type
– select the type of the input (NO or NC).