Object Instance
Functional Description
Read or Write
Analog Inputs
AI - 1
Analog Input 1 (default: Fume Hood Face Velocity)
Read-Only
AI - 17
Analog Input 2 (default: Secondary Face Velocity)
Read-Only
AI - 18
Analog Input 3 (default: Sash Position Sensor)
Read-Only
AI - 19
Analog Input 4 (default: Exhaust Air Flow Volume)
Read-Only
AI - 20
Thermistor Input 1 (default: Ambient Temperature)
Read-Only
AI - 21
Thermistor Input 2 (default: spare temperature input)
Read-Only
Analog Outputs
AO - 1
Analog Output 1 (default: Primary Exhaust Damper Control)
Read-Only
AO - 11
Analog Output 2 (default: Supply/Exhaust Damper Control)
Read-Only
AO - 12
Analog Output 3 (spare control output)
Read-Only
AO - 13
Analog Output 4 (spare control output)
Read-Only
Binary Inputs
BI - 3
Digital Input 1 (default: Fume Hood Sash Switch)
Read-Only
BI - 4
Digital Input 2 (default: Secondary Sash Switch)
Read-Only
BI - 5
Digital Input 3 (spare digital input)
Read-Only
BI - 6
Digital Input 4 (spare digital input)
Read-Only
Binary Outputs
BO - 1
Relay Output 1 (default: Primary Alarm Relay Output)
Read-Only
BO - 2
Relay Output 2 (spare relay output)
Read-Only
BO - 3
Relay Output 3 (spare relay output)
Read-Only
BO - 4
Relay Output 4 (spare relay output)
Read-Only
Internal Float Values
ADF - 1
PID Control Loop 1 Setpoint (Fume Hood Face Velocity Setpoint)
Read/Write
ADF - 2
Primary Alarm Relay High Setpoint
Read/Write
ADF - 3
Primary Alarm Relay Low Setpoint
Read/Write
ADF - 4
Secondary Alarm Relay High Setpoint
Read/Write
ADF - 5
Secondary Alarm Relay Low Setpoint
Read/Write
ADF - 8
AI-1 Low Alarm Setpoint (Low Face Velocity Alarm Setpoint)
Read/Write
ADF - 9
AI-1 Low Warning Setpoint (Low Face Velocity Warning Setpoint)
Read/Write
ADF - 10
AI-1 High Warning Setpoint (High Face Velocity Warning Setpoint)
Read/Write
ADF - 11
AI-1 High Alarm Setpoint (High Face Velocity Alarm Setpoint)
Read/Write
ADF - 13
PID Control Loop 2 Setpoint
Read/Write
ADF - 14
PID Control Loop 3 Setpoint
Read/Write
ADF - 15
PID Control Loop 4 Setpoint
Read/Write
ADF - 16
Air Change Rate based on Flow Input at AI-1
Read-Only
ADF - 17
Air Change Rate based on Flow Input at AI-2
Read-Only
ADF - 18
Air Change Rate based on Flow Input at AI-3
Read-Only
ADF - 19
Air Change Rate based on Flow Input at AI-4
Read-Only
The following table itemizes the list of points available for integration in a building management system (BMS). This table contains the objects for
open N2 integration.