TT100
·
85
·
Function
Section
Function
Code
Function
Definition
Setting Range
Mfr’s
Value
Change
Mot
or
param
et
ers
F800
Motor‟s parameters
selection
Setting range:
0: no parameter measurement;
1:Stator resistance parameter measurement;
0
╳
F801
Rated power
0.2
~
1000KW
╳
F802
Rated voltage
1
~
440V
╳
F803
Rated current
0.1
~
6500A
╳
F804
Number of motor poles
2
~
100
4
╳
F805
Rated rotary speed
1
~
30000
╳
F806
Stator resistance
0.001
~
65.00Ω
╳
F807~F809 Reserved
F810
Motor rated frequency
1.0~650.0Hz
50.00
╳
F811~F830 Reserved
C
om
m
uni
cat
ion
Paramet
er
F900
Communication
Address
1~255: single inverter address
0: broadcast address
1
√
F901
Communication Mode 1: ASCII 2: RTU
3: Remote controlling keypad
1
√
F902
Reserved
F903
Odd/Even Calibration
0: no calibration 1: odd calibration
2: even calibration
0
√
F904
Baud Rate
0
:
1200
;
1
:
2400
;
2
:
4800
;
3
:
9600 ; 4
:
19200 5: 38400
6: 57600
3
√
F905
~
F930 Reserved
PID
Par
am
et
ers
FA00
Polarity
0: positive feedback
1: negative feedback
0
╳
FA01
Reference Source
0: Given Digit 1: AI1
2: AI2 3: Input pulse given;
4~5: Reserved
0
╳
FA02
Given
Digit
Reference
Source
0.0
~
100.0
50.0
√
FA03
Feedback Source
0: AI1 1: AI2
2: Input pulse frequency;
3~5: Reserved
0
╳
FA04
Proportion Coefficient
0.0
~
100.0
20.0
√
FA05
Integral Time
0.1
~
10.0S
2.0
√
FA06
Precision
0.0
~
20.0
0.1
√
FA07
Show value of min feedback
0
~
9999
0
√
FA08
Show value of max feedback
0
~
9999
1000
√
FA09
Reserved
FA10
Dormancy function
selection
0: Invalid 1: Valid
0
√
FA11
Dormancy waking
value
0~100 (%)
10
√