TT100
·
22
·
⑥
Enter F800 parameter and set it to 1 to allow measuring the parameter of the motor
⑦
Press the “Run” key, to measure the parameters of the motor. After completion of the measurement,
and relevant parameters will be stored in F806. For the details of measurement of motor parameters,
please refer to “Operation process of measuring the motor parameters” in this manual and Chapter
XII of this manual.
(4) Set functional parameters of the inverter:
①
Enter F203 parameter and set it to 0;
②
Enter F111 parameter and set the frequency to 50.00Hz;
③
Enter F200 parameter and set it to 0; select the mode of start as keypad control;
④
Enter F201 parameter and set it to 0; select the mode of stop as keypad control;
⑤
Enter F202 parameter and set it to 0; select forward locking.
(5) Press the “Run” key, to start the inverter;
(6) During running, current frequency of the inverter can be changed by pressing ▲ or ▼;
(7) Press the “Stop/Reset” key once, the motor will decelerate until it stops running;
(8) Switch off the air switch, and power off the inverter.
4.9.2 Operation process of setting the frequency with keypad panel, and starting,
forward and reverse running, and stopping inverter through control terminals
(1) Connect the wires in accordance with Figure 4-2. After having checked the wiring successfully,
switch on the air switch, and power on the inverter;
Figure 4-2 Wiring Diagram 2
(2) Press the “Fun” key, to enter the programming menu.
(3) Study the parameters of the motor: the operation process is the same as that of example 1.
(4) Set functional parameters of the inverter:
①
Enter F203 parameter and set it to 0; select the mode of frequency setting to digital given memory;
②
Enter F111 parameter and set the frequency to 50.00Hz;
③
Enter F208 parameter and set it to 1; select two-line control mode 1 (Note: when F208 ≠0, F200,
F201 and F202 will be invalid.)
(5) Close the switch OP3, the inverter starts forward running;
(6) During running, current frequency of the inverter can be changed by pressing ▲ or ▼;
PE
OP3
OP4
OP6
S/L2
R/L1
T/L3
AC400V