42
·
programmed with “reaching the set count values” function when a certain number of pulses are input
from OP1, until count value reaches the “set times”.
As shown in Fig 5-6: if F313=1
、
F314
=
8
,
F315
=
5
,
F300
=
9, relay will output an instruction signal
when OP1 inputs the 5
th
pulse, relay will output an instruction signal until reaching “set count times 8”.
1 2 3 4 5 6 7 8 1
OP1 Input:
DO1:
Relay:
5.3.2 Digital multifunctional input terminals
.
F316 OP1 terminal function setting
Setting range:
0: no function;
1: running terminal;
2: stop terminal;
3: multi-stage speed terminal 1;
4: multi-stage speed terminal 2;
5: multi-stage speed terminal 3;
6: multi-stage speed terminal 4;
7: reset terminal;
8: free stop terminal;
9: external emergency stop terminal;
10: acceleration/deceleration forbidden terminal;
11: forward run jogging;
12: reverse run jogging;
13: UP frequency increasing terminal;
14: DOWN frequency decreasing terminal;
15: “FWD” terminal;
16: “REV” terminal;
17: three-line type input “X” terminal;
18: acceleration/deceleration time switchover terminal;
19~20: Reserved;
21: frequency source switchover terminal;
22: Count input terminal:
23: Count reset terminal; 24~30: reserved
Mfr‟s value: 11
F317 OP2 terminal function setting
Mfr‟s value: 9
F318 OP3 terminal function setting
Mfr‟s value: 15
F319 OP4 terminal function setting
Mfr‟s value: 16
F320 OP5 terminal function setting
Mfr‟s value: 7
F321 OP6 terminal function setting
Mfr‟s value: 8
F322 OP7 terminal function setting
Mfr‟s value: 1
F323 OP8 terminal function setting
Mfr‟s value: 2
·This parameter is used for setting the corresponding function for multifunctional digital input terminal.
·Both free stop and external emergency stop of the terminal have the highest priority.
·When pulse given is selected, OP1 terminal is set as pulse signal input terminal automatically.
Note: 15KW inverter and below 15KW has 6 multifunctional digital input terminals OP1~OP6.
Table 5-3 Instructions for digital multifunctional input terminal
Value
Function
Instructions
Fig 5-6
Set Count times & Designated Count Times