TT100
·
47
·
F414 Upper limit of AI3 channel input
Setting range: F412
~
10.0V
Mfr‟s value: 10.0V
F415 Corresponding setting for upper limit of AI3 input
Setting range:
Max (1.00
,
F413)
~
2.00
Mfr‟s value: 2.00
F416 AI3 channel proportional gain K1
Setting range: 0.0
~
10.0
Mfr‟s value: 1.0
F417 AI3 filtering time constant
Setting range: 0.1
~
10.00
Mfr‟s value: 0.10
The function of AI2 and AI3 is the same with AI1.
F418 AI1 channel 0Hz voltage dead zone
Setting range:
0
~
0.50V (Positive-Negative)
Mfr‟s value: 0.00
F419 AI2 channel 0Hz voltage dead zone
Setting range:
0
~
0.50V (Positive-Negative)
Mfr‟s value: 0.00
F420 AI3 channel 0Hz voltage dead zone
Setting range:
0
~
0.50V (Positive-Negative)
Mfr‟s value: 0.00
Analog input voltage 0-5V can correspond to output frequency -50Hz-50Hz (2.5V corresponds to 0Hz) by
setting the function of corresponding setting for upper / lower limit of analog input. The group function codes of
F418, F419 and F420 set the voltage range corresponding to 0Hz. For example, when F418=0.5, F419=0.5 and
F420=0.5, the voltage range from (2.5-0.5=2) to (2.5+0.5=3) corresponds to 0Hz. So if F418=N, F419=N and
F420=N, then 2.5±N should correspond to 0Hz. If the voltage is in this range, inverter will output 0Hz.
0HZ voltage dead zone will be valid when corresponding setting for lower limit of input is less than 1.00.
TT100 series inverters have two analog output channels.
The greater the setting value of F437 is, the steadier the detecting analog is, but the response speed will
decrease. Please set it according to the actual situations.
F460 AI1channel input mode
Setting range: 0: straight line mode
1: folding line mode
Mfr‟s value: 0
F461 AI2 channel input mode
Setting range: 0: straight line mode
1: folding line mode
Mfr‟s value: 0
F462 AI1 inseration point A1 voltage value Setting range: F400
~
F464
Mfr‟s value: 2.00V
F463 AI1 inseration point A1 setting value Setting range: F401
~
F465
Mfr‟s value: 1.40
F464 AI1 inseration point A2 voltage value Setting range: F462
~
F466
Mfr‟s value: 3.00V
F465 AI1 inseration point A2 setting value Setting range: F463
~
F467
Mfr‟s value: 1.60
F466 AI1 inseration point A3 voltage value Setting range: F464
~
F402
Mfr‟s value: 4.00V
F467 AI1 inseration point A3 setting value Setting range: F465
~
F403
Mfr‟s value: 1.80
F468 AI2 inseration point B1 voltage value Setting range: F406
~
F470
Mfr‟s value: 2.00V
F469 AI2 inseration point B1 setting value Setting range: F407
~
F471
Mfr‟s value: 1.40
F470 AI2 inseration point B2 voltage value Setting range: F468
~
F472
Mfr‟s value: 3.00V
F471 AI2 inseration point B2 setting value Setting range: F469
~
F473
Mfr‟s value: 1.60
F472 AI2 inseration point B3 voltage value Setting range: F470
~
F412
Mfr‟s value: 4.00V
F473 AI2 inseration point B3 setting value Setting range: F471
~
F413
Mfr‟s value: 1.80
When analog channel input mode selects straight-line, please set it according to the paremeters from F400 to
F437 Analog filter width
Setting range: 1
~
100
Mfr‟s value:10