TT100
·
4
·
Protection
level
IP20
Applicable
Motor
0.2
~
15KW
1.6 Designed Standards for Implementation
IEC/EN 61800-5-1: 2003 Adjustable speed electrical power drive systems
safety requirements.
IEC/EN 61800-3: 2004 Adjustable speed electrical power drive systems-Part
3: EMC product standard including specific test methods.
1.7 Safe instructions
Please check the model in the nameplate of the inverter and the rated value of
the inverter. Please do not use the damaged inverter in transit.
Installation and application environment should be free of rain, drips, steam,
dust and oily dirt; without corrosive or flammable gases or liquids, metal
particles or metal powder. Environment temperature within the scope of -10
℃
~
+50
℃
.
Please install inverter away from combustibles.
Do not drop anything into the inverter.
The reliability of inverters relies heavily on the temperature. The around
temperature increases by 10
℃
, inverter life will be halved. Because of the wrong
installation or fixing, the temperature of inverter will increase and inverter will
be damaged.
If inverter is installed in a control cabinet, smooth ventilation should be ensured
and inverter should be installed vertically. If there are several inverters in one
cabinet, in order to ensure ventilation, please install inverters side by side. If it is
necessary to install several inverters up and down, please add heat-insulation
plate.