TT100
·
43
·
0
No function
Even if signal is input, inverter will not work. This function can be
set by undefined terminal to prevent mistake action.
1
Running terminal
When running command is given by terminal or terminals
combination and this terminal is valid, inverter will run. This
terminal has the same function with “run” key in keypad.
2
Stop terminal
When stop command is given by terminal or terminals combination
and this terminal is valid, inverter will stop. This terminal has the
same function with “stop” key in keypad.
3
Multistage speed terminal 1
15-stage speed is realized by combination of this group of
terminals. See table 5-4.
4
Multistage speed terminal 2
5
Multistage speed terminal 3
6
Multistage speed terminal 4
7
Reset terminal
This terminal has the same function with “reset” key in keypad.
Long-distance malfunction reset can be realized by this function.
8
Free stop terminal
Inverter closes off output and motor stop process is not controlled
by inverter. This mode is often used when load has big inertia or
there are no requirements for stop time. This mode has the same
function with free stop of F209.
9
External emergency
stop terminal
When external malfunction signal is given to inverter,
malfunction will occur and inverter will stop.
10
Acceleration/deceleration
forbidden terminal
Inverter will not be controlled by external signal (except for stop
command), and it will run at the current output frequency.
11
forward run jogging
Forward jogging running and reverse jogging running. Refer to
F124, F125 and F126 for jogging running frequency, jogging
acceleration/deceleration time.
12
reverse run jogging
13
UP frequency increasing
terminal
When frequency source is set by digital given, the setting
frequency can be adjusted which rate is set by F211.
14
DOWN frequency
decreasing terminal
15
“FWD” terminal
When start/stop command is given by terminal or terminals
combination, running direction of inverter is controlled by
external terminals.
16
“REV” terminal
17
Three-line input “X”
terminal
“FWD”
、
“REV”
、
“CM” terminals realize three-line control. See
F208 for details.
18
acceleration/deceleration
time switchover terminal
When this function is selected, second acceleration/deceleration
time is valid. See F116 and F117 for the second
acceleration/deceleration time.
19
Reserved
Reserved
20
Reserved
Reserved
21
frequency source
switchover terminal
When F207=2, main frequency source(X) and accessorial frequency
source(Y) can be switched over by frequency source switching
terminal. When F207=3, X and (X + Y) can be switched over by
frequency source switching terminal.
22
Count input terminal
Built-in count pulse input terminal.
23
Count reset terminal
Reset terminal count value to zero.
24-30
Reserved
Reserved