29
Performance
Data
SSP-PRC002-EN
Table PD-23— Discharge Plenum And Grille Assembly Throw Distance — Air Handler — ft (m)
Unit
Louver Angle Deflection Position
Model No.
CFM
m
3
/h
Straight
20
40
55
1400
2378
38 (11.6)
24 (7.3)
22 (6.7)
18 (5.5)
1600
2718
42 (12.8)
31 (9.4)
26 (7.9)
20 (6.1)
TWE050
1800
3058
46 (14.0)
37 (11.3)
29 (8.8)
22 (6.7)
2000
3398
48 (14.6)
43 (13.1)
33 (10.1)
24 (7.3)
2200
3737
51 (15.5)
50 (15.2)
36 (11.0)
25 (7.6)
2100
3568
49 (14.9)
38 (11.6)
31 (9.4)
27 (8.2)
2400
4077
52 (15.9)
43 (13.1)
35 (10.7)
29 (8.8)
2700
4587
55 (16.8)
48 (14.6)
38 (11.6)
31 (9.4)
TWE075
3000
5097
58 (17.7)
53 (16.2)
42 (12.8)
32 (9.8)
3200
5436
56 (17.1)
46 (14.0)
38 (11.6)
30 (9.1)
3600
6116
62 (18.9)
51 (15.5)
42 (12.8)
33 (10.1)
4000
6795
66 (20.1)
57 (17.4)
47 (14.3)
35 (10.7)
4400
7475
71 (21.6)
62 (18.9)
52 (15.9)
38 (11.6)
TWE100
4800
8154
76 (23.2)
67 (20.4)
56 (17.1)
42 (12.8)
4300
7305
42 (12.8)
32 (9.8)
29 (8.8)
21 (6.4)
4900
8324
47 (14.3)
38 (11.6)
32 (9.8)
25 (7.6)
5400
9174
52 (15.9)
44 (13.4)
37 (11.3)
29 (8.8)
TWE155
5600
9514
50 (15.2)
40 (12.2)
33 (10.1)
27 (8.2)
6000
10193
57 (17.4)
49 (14.9)
41 (12.5)
32 (9.8)
6400
10873
56 (17.1)
46 (14.0)
38 (11.6)
30 (9.1)
7200
12232
62 (18.9)
51 (15.5)
42 (12.8)
33 (10.1)
TWE200
8000
13591
66 (20.1)
57 (17.4)
47 (14.3)
35 (10.7)
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw
factor:
Terminal Velocity
Throw Factor
50 fpm (.25 m/s)
x
1.50
100 fpm (.51 m/s)
x
.75
150 fpm (.76 m/s)
x
.50
Table PD-24— Static Pressure Drop Through Accessories (Inches Of Water Column)
1
— Air Handler
Discharge
Electric Heaters (kW)
Unit
Return Grille
Plenum and Grille
2
5-10
15-20
25-30
35-50
Model No.
CFM
m
3
/h
In. wc
1
Pascal
In. wc
1
Pascal
In. wc (Pascal)
1400
2380
.09
(22.4)
.16
(39.8)
.06 (15.0)
.06 (15.0)
.12 (29.9)
—
TWE050A
1600
2718
.12
(29.9)
.21
(52.3)
08 (19.9)
.08 (19.9)
.14 (34.9)
—
2000
3398
.18
(44.8)
.33
(82.2)
.13 (32.4)
.13 (32.4)
.19 (47.3)
—
2100
3568
.05
(12.5)
.19
(47.3)
.02 (5.0)
.03 (7.5)
.05 (12.5)
.08 (19.9)
TWE075A
2400
4079
.08
(19.9)
.27
(67.2)
.03 (7.5)
.06 (15.0)
.08 (19.9)
.12 (29.9)
3000
5098
.13
(32.4)
.40
(99.6)
.06 (15.0)
.12 (29.9)
.17 (42.4)
.23 (57.3)
TWE100A
2800
4756
.04
(10.0)
.34
(84.7)
.03 (7.5)
.04 (10.0)
.14 (34.9)
.20 (49.8)
TWE100B
3200
5436
.07
(17.4)
.43
(107.1)
.06 (15.0)
.13 (32.4)
.19 (47.3)
.26 (64.8)
4300
7304
.07
(17.4)
.18
(44.8)
.02 (5.0)
.02 (5.0)
.04 (10.0)
.05 (12.5)
TWE155B
4800
8154
.09
(22.4)
.23
(57.3)
.03 (7.5)
.03 (7.5)
.06 (15.0)
.08 (19.9)
6000
10195
.15
(37.4)
.34
(84.7)
.06 (15.0)
.06 (15.0)
.12 (29.9)
.17 (42.4)
5600
9515
.07
(17.4)
.32
(79.7)
.04 (10.0)
.04 (10.0)
.10 (25.0)
.15 (37.4)
TWE200B
6400
10872
.11
(27.4)
.43
(107.1)
.06 (15.0)
.06 (15.0)
.13 (32.4)
.19 (47.3)
8000
13594
.17
(42.3)
.66
(164.3)
.10 (25.0)
.10 (25.0)
.20 (49.8)
.30 (74.7)
1. Return air filter ESP included in Fan Performance Table data.
2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installer’s Guide.