(System)
Table PD-10 — Gross Heating Capacities (kW)
TWA100A Heat Pump with TWE100A Air Handler At 5649 m
3
/h (SI)
Outdoor
Heating Capacity (kW) At
Total Power in Kilowatts At
Temperature
Indicated Indoor Dry Bulb Temperature
Indicated Indoor Dry Bulb Temperature
(°C)
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
6.0
10.9
12.1
12.8
5.5
6.0
6.2
6.5
-25.0
9.2
12.2
13.1
13.6
5.6
6.1
6.3
6.6
-22.2
11.4
13.5
14.2
14.6
5.7
6.2
6.5
6.7
-19.4
13.3
14.9
15.3
15.6
5.8
6.3
6.6
6.9
-16.7
15.2
16.3
16.6
16.8
5.9
6.5
6.7
7.0
-13.9
17.0
17.7
17.9
18.0
6.0
6.6
6.9
7.2
-11.1
18.8
19.3
19.4
19.4
6.2
6.7
7.0
7.4
-8.3
20.6
20.9
20.9
20.9
6.3
6.9
7.2
7.5
-5.6
22.5
22.6
22.5
22.5
6.5
7.0
7.4
7.7
-2.8
24.5
24.4
24.3
24.1
6.6
7.2
7.5
7.9
0.0
26.5
26.3
26.1
26.0
6.8
7.4
7.7
8.1
2.8
28.6
28.2
28.0
27.8
6.9
7.6
7.9
8.3
5.6
30.6
30.1
29.9
29.7
7.1
7.8
8.1
8.5
8.3
32.8
32.2
31.9
31.7
7.3
8.0
8.4
8.8
11.1
35.0
34.3
34.0
33.7
7.5
8.2
8.6
9.0
13.9
37.2
36.5
36.2
35.9
7.7
8.4
8.8
9.2
16.7
39.5
38.7
38.3
38.0
7.9
8.7
9.1
9.5
19.4
41.7
40.9
40.5
40.2
8.1
8.9
9.3
9.8
22.2
44.1
43.2
42.8
42.4
8.4
9.2
9.6
10.0
Correction Factors - Other Airflows
(Table Value x Correction Factor = Value at new airflow)
Airflow
3000 cfm
3675 cfm
5097 m
3
/h
6243 m
3
/h
Heating Capacity
x 0.99
x 1.01
Compressor kW
x 1.02
x 0.98
Values at ARI Rating Conditions of:
70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)
70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond)
Airflow = 3325 cfm (5649 m
3
/h)
Heating Capacity (High Temp.) = 110,000 (32.21)
Heating Capacity (Low Temp.) = 71,000 (20.79)
Compressor Power (High Temp) = 7.59 kW
Compressor Power (Low Temp) = 6.60 kW
Coeff. Of Perf. (High Temp) = 3.4
Coeff. Of Perf. (Low Temp) = 2.4
Outdoor Fan Power = 615 watts
Indoor Fan Power = 1,030 watts
Note:
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.
Table PD-10 — Gross Heating Capacities (MBh)
TWA100A Heat Pump with TWE100A Air Handler At 3325 CFM (I-P)
Outdoor
Heating Capacity (Btu/1000) At
Total Power in Kilowatts At
Temperature
Indicated Indoor Dry Bulb Temperature
Indicated Indoor Dry Bulb Temperature
(°F)
60
70
75
80
60
70
75
80
-18
20.4
37.3
41.2
43.6
5.7
7.3
7.9
8.5
-13
31.4
41.8
44.6
46.4
6.2
7.5
8.0
8.6
-8
39.0
46.3
48.4
49.7
6.5
7.6
8.1
8.6
-3
45.5
50.8
52.4
53.3
6.8
7.8
8.2
8.7
2
51.8
55.6
56.7
57.3
7.0
7.9
8.4
8.8
7
57.9
60.6
61.3
61.6
7.2
8.0
8.5
9.0
12
64.1
65.8
66.2
66.3
7.3
8.2
8.6
9.1
17
70.4
71.3
71.4
71.3
7.5
8.3
8.7
9.2
22
76.9
77.1
77.0
76.7
7.6
8.4
8.9
9.4
27
83.6
83.3
82.9
82.5
7.8
8.6
9.0
9.5
32
90.7
89.7
89.2
88.7
7.9
8.8
9.2
9.7
37
97.6
96.2
95.5
94.9
8.1
8.9
9.4
9.9
42
104.6
102.9
102.1
101.4
8.2
9.1
9.6
10.1
47
112.0
109.9
109.0
108.2
8.4
9.3
9.7
10.3
52
119.5
117.2
116.2
115.2
8.6
9.5
10.0
10.5
57
127.1
124.6
123.5
122.5
8.8
9.7
10.2
10.7
62
134.8
132.1
130.8
129.7
9.0
9.9
10.4
11.0
67
142.6
139.7
138.3
137.2
9.2
10.1
10.7
11.2
72
150.7
147.5
146.1
144.8
9.4
10.4
10.9
11.5