Air Handlers

General

Air handler units shall be completely
factory assembled including coil,
condensate drain pan, fan motor(s),
filters, and controls in an insulated
casing that can be applied in either
vertical or horizontal configuration. Unit
shall be rated and tested in accordance
with ARI standard 340/360. Unit shall be
UL listed and labeled in accordance with
UL 1995 for indoor blower coil units.

Casing

Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Casing shall be completely insulated
with cleanable, foil faced, fire-retardant,
permanent, odorless, glass fiber
material. All insulation edges shall be
either captured or sealed. Knockouts
shall be provided for unit electrical
power and refrigerant piping
connections. Captive screws shall be
standard on all access panels.

Refrigeration System

The TWE050A, TWE075A, TWE100A  units
shall have a single refrigeration circuit
and  the TWE100B, TWE155B, TWE200B
units shall have dual refrigeration
circuits. Each refrigeration circuit is
controlled by a factory installed thermal
expansion valve.

Evaporator Coil

Configured aluminum fin surface shall
be mechanically bonded to 3/8" (10 mm)
internally enhanced copper tubing and

Condenser Coil Guard

 — Metal grille

with PVC coating shall be provided to
alleviate coil damage.

Black Epoxy Coated Condenser Coi

l —

This factory installed option is designed
to provide corrosion protection of air
cooled condenser coils for seacoast
application.  The black epoxy coil
protection is a factory applied thermoset
vinyl coating, bonded to normal
aluminum fin stock.  The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B177.

shall be factory pressure and leak tested
at 375 psig (2586 kPa). Coil is arranged
for draw-through airflow and shall
provide a double sloped condensate
drain pan constructed of PVC plastic. The
drain pan shall be removable for
cleaning. The condensate drain pan can
be installed in any of four positions
allowing for vertical or horizontal
application and providing external
connections on either side of the unit.

Evaporator Fan

Double inlet, double width, forward
curved, centrifugal-type fan(s) with
adjustable belt drive shall be standard.
Thermal overload protection shall be
standard on motor. Fan and motor
bearings shall be permanently
lubricated. Oversized motors shall be
available as an option for high static
application. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT).

Controls

Magnetic evaporator fan contactor, low
voltage terminal strip, check valve(s), and
single point power entry shall be
included. All necessary controls shall be
factory-installed and wired. Evaporator
defrost control shall be included to
prevent compressor slugging by
temporarily interrupting compressor
operation when low evaporator coil
temperatures are encountered.

Filters

One inch, throw-away filters shall be
standard on TWE050A, TWE075A,
TWE100A and TWE120B model air
handlers. Filters shall be accessible from
the side coil access panel. Filter rack can
be field converted to two inch capability.
Two inch, throw-away filters shall be
standard on TWE155B and TWE200B
models.

ACCESSORIES

Electric Heaters

 — UL and CSA

approved electric heat modules shall be
available for installation directly on fan
discharge. Electric heaters shall be
available in a wide range of capacities
with one or two stage control, single-
point electric power connection, and
terminal strip connections. Electric
heater elements shall be constructed of
heavy-duty nickel chromium elements
internally wye connected on 400 volt,

three phase. Each 400 volt heater shall
have automatic line break high limit
controls.

Discharge Plenums and Grilles

 —

Accessory discharge plenums shall be
available for vertical, free discharge
applications. Plenums shall be
constructed of heavy-gauge, zinc coated,
galvanized steel finished with baked
enamel to match the air handler unit.
Grilles shall be satin finished aluminum
and have four-way adjustable louvers.

Return Air Grilles

 — Accessory return air

grille shall be provided for vertical front,
free return applications. Grilles shall be
installed in place of the front lower side
panel. Grille shall be satin finished
aluminum with non-adjustable louvers.

Mounting Subbase

 

— The  accessory

shall be available for vertical floor mount
configurations. Subbase shall be
constructed of heavy gauge, zinc coated,
galvanized steel with baked enamel
finish to match air handler unit. Subbase
is required in the vertical air flow
application for condensate drain
trapping and when isolators are
required.

Vibration Isolator

s

 — This accessory

shall reduce transmission of noise and
vibration to building structures,
equipment, and adjacent spaces.
Packages shall be available in either
neoprene-in shear or spring-flex types in
floor or suspended mountings.

Oversized Motors

 — Field installed

oversized motors shall be available for
high static pressure applications.

CONTROL OPTIONS

Standard Indoor Thermostats

 — Two

stage heating and cooling operation or
one stage heating and cooling
thermostats shall be available in either
manual or automatic changeover.

Programmable Electronic Night Setback
Thermostat

 — The option shall provide

heating setback and cooling setup with 7-
day programming capability.

Outdoor Thermostat

 

— This  option

shall provide staging control of
electric heaters based on a set
outdoor temperature.

Mechanical
Specifications

Summary of Contents for TWE050A

Page 1: ...Split System Heat Pumps Split System Heat Pumps TWA075A TWA200B Air Handlers TWE050A TWE200B 50 Hz SSP PRC002 EN January 2004...

Page 2: ...me saving colored and numbered wiring and removable panels which allow complete access to all major components and controls All outdoor units feature external high and low pressure switches for easy d...

Page 3: ...oduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cool and Heat Performance Fan Performance Electric Power Connection...

Page 4: ...ime and money for rigging and installation And the compactness will permitTrane s unit to replace almost any unit effortlessly LowAmbient Cooling Operation Each heat pump unit can operate to 50 F 10 C...

Page 5: ...A Full Line ofThermostats OutdoorThermostat Odyssey Lowers Installation Costs Your installation costs are reduced with Odyssey Both outdoor units and air handlers are factory packaged and assembled s...

Page 6: ...rement for a head pressure control to allow low ambient cooling Application of this product should be within the catalogued airflow and performance considerations Clearance Requirements The recommende...

Page 7: ...or Heat 3 5 x bhp MBh 3 5 x 1 07 3 75 MBh 1 375 x kW kW 1 375 x 0 8 1 1 kW NetTotal Cooling Capacity 85 1 MBh 3 75 81 35 MBh 24 9 kW 1 1 23 8 kW Net Sensible Cooling Capacity 60 8 MBh 3 75 57 05 MBh 1...

Page 8: ...4 5 6 7 8 9 10 11 12 Air Handler Model Nomenclature Digit 8 Electrical Characteristics D 380 415 3 50 Digits 1 2 3 ProductType TWE Cooling Convertible Digits 4 5 6 Nominal Gross Cooling Capacity MBh...

Page 9: ...g 18 0 8 16 31 5 14 29 Notes 1 Cooling Performance is rated at 95 F 35 C ambient 80 F 26 7 C entering dry bulb 67 F 19 4 C entering wet bulb and nominal cfm listed ARI rating cfm is 350 cfm ton for th...

Page 10: ...e lb7 kg 36 0 16 33 48 5 22 0 Notes 1 Cooling Performance is rated at 95 F 35 C ambient 80 F 26 7 C entering dry bulb 67 F 19 4 C entering wet bulb and nominal cfm listed ARI rating cfm is 350 cfm ton...

Page 11: ...ers Type Throwaway Throwaway Throwaway Throwaway Furnished Yes Yes Yes Yes No 1 1 3 4 4 Recommended Size in mm 16x20x1 20x20x1 16x25x1 16x25x1 16x25x1 406 4x508x25 4 406 4 635 25 4 406 4 635 25 4 406...

Page 12: ...1 8 73 6 82 5 82 5 82 6 82 6 87 3 71 9 Note All temperatures are in degrees Fahrenheit Airflow is in cfm Table PD 1 Gross Cooling Capacities kW TWA075A Heat Pump with TWE075A Air Handler SI AmbientTem...

Page 13: ...2 90 119 9 119 9 120 7 120 2 130 4 98 3 116 2 116 2 116 1 116 1 125 4 96 3 112 2 112 2 112 2 112 2 120 3 94 3 108 1 108 1 108 1 108 1 114 9 92 3 Note All temperatures are in degrees Fahrenheit Airflo...

Page 14: ...65 4 152 9 180 4 120 3 154 6 154 6 157 3 149 4 171 4 116 9 90 181 5 181 5 181 7 181 7 196 3 152 1 176 2 176 2 176 4 176 4 189 1 149 3 169 9 169 9 170 1 170 1 180 9 146 2 162 9 162 9 163 1 163 1 171 9...

Page 15: ...3 216 2 199 8 235 1 156 3 203 2 203 2 206 6 195 7 224 4 152 2 90 237 7 237 7 237 6 237 6 256 0 197 4 230 1 230 1 230 0 230 0 246 0 193 5 222 1 222 1 222 0 222 0 235 6 189 5 213 7 213 7 213 6 213 6 22...

Page 16: ...7 75 7 89 8 04 8 19 Head pressure kPA 2206 2255 2305 2357 2411 2467 46 1 Capacity kW 16 4 18 0 19 8 21 5 23 4 25 2 OD Unit Power kW 8 32 8 45 8 59 8 72 8 87 9 02 Table PD 5 Gross Cooling Performance M...

Page 17: ...Btuh 1000 74 2 82 1 90 3 98 8 107 6 116 4 OD Unit KW 11 02 11 22 11 42 11 63 11 83 12 02 Table PD 6 Gross Cooling Performance kW TWA100A Heat Pump Only SI ODTemp Suction ReferenceTemperature C C 1 1...

Page 18: ...p Btuh 1000 110 6 122 0 133 7 145 9 158 4 171 2 OD Unit KW 16 26 16 51 16 77 17 04 17 32 17 62 Table PD 7 Gross Cooling Performance kW TWA155B Heat Pump Only SI ODTemp Suction ReferenceTemperature C C...

Page 19: ...p Btuh 1000 145 0 160 1 175 7 191 8 208 2 224 8 OD Unit KW 22 32 22 80 23 30 23 79 24 27 24 73 Table PD 8 Gross Cooling Performance kW TWA200B Heat Pump Only SI ODT emp Suction ReferenceTemperature C...

Page 20: ...4 4 53 6 53 4 53 2 5 8 6 3 6 6 7 0 27 59 2 58 6 58 4 58 2 5 9 6 4 6 8 7 1 32 64 5 63 9 63 7 63 5 6 0 6 6 6 9 7 3 37 69 9 69 4 69 1 68 8 6 1 6 7 7 1 7 5 42 75 7 75 1 74 7 74 3 6 2 6 9 7 2 7 6 47 81 8 8...

Page 21: ...nditions of 70F 21 1C and47 43F 8 3 6 1C HighTemp Cond 70F 21 1C and17 15F 8 3 9 4C LowTemp Cond Airflow 3325 cfm 5649 m3 h Heating Capacity High Temp 110 000 32 21 Heating Capacity Low Temp 71 000 20...

Page 22: ...re Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature C 15 6 21 1 23 9 26 7 15 6 21 1 23 9 26 7 27 8 20 1 17 8 17 0 16 4 5 5 6 0 6 2 6 5 25 0 20 9 18 8 18 1 17 5 5 6 6 1 6 3 6 6...

Page 23: ...rature Indicated Indoor Dry BulbTemperature Indicated Indoor Dry BulbTemperature C 15 6 21 1 23 9 26 7 15 6 21 1 23 9 26 7 27 8 12 4 23 2 24 8 25 6 5 5 6 0 6 2 6 5 25 0 20 0 25 3 26 4 27 0 5 6 6 1 6 3...

Page 24: ...tments are made in 0 5 turn increments Table PD 14 Blower Speeds TWE050A Motor DriveTurns Open Drive 6 5 4 3 2 1 0 Standard N A 590 639 688 737 786 835 High Static N A 713 772 832 891 951 1009 Table P...

Page 25: ...818 0 66 3547 453 0 34 499 0 39 546 0 43 592 0 47 638 0 51 684 0 55 730 0 59 771 0 63 798 0 67 825 0 72 3755 463 0 37 510 0 41 556 0 45 602 0 5 649 0 54 695 0 59 742 0 63 776 0 68 804 0 72 831 0 77 39...

Page 26: ...0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 1 20 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 5 HP Standard Motor and Low Static Drive 2600 460 0 32 493 0...

Page 27: ...mm throwaway filters 2 Tabulated brake horsepower is the motor shaft output required 3 Factory setting of motor sheave is 1 5 turns open Adjustments are made in 0 5 turn increments Table PD 19 Evapora...

Page 28: ...inch 51 mm throwaway filters 2 Tabulated brake horsepower is the motor shaft output required 3 Factory setting of motor sheave is 1 5 turns open Adjustments are made in 0 5 turn increments 4 Low stat...

Page 29: ...terminal velocities may be established by multiplying throw distances in table above by throw factor Terminal Velocity Throw Factor 50 fpm 25 m s x 1 50 100 fpm 51 m s x 75 150 fpm 76 m s x 50 Table P...

Page 30: ...39 1 10 39 35 457 10 39 35 457 10 39 17 31 2 10 39 35 457 10 39 6 92 23 606 6 92 59 063 17 31 TWE075 100A 100 24 22 2 13 83 47 213 13 83 10 39 35 457 10 39 82 670 24 22 TWE155 200 6 94 1 6 94 23 701...

Page 31: ...0 380 415 2 15 TWE075 380 415 4 15 TWE100 380 415 5 15 TWE155 380 415 6 15 TWE200 380 415 10 15 Table ED 4 UnitWiring Heat Pumps Minimum Maximum Fuse Unit Unit Operating Circuit Size or Maximum Model...

Page 32: ...12 15 BAYHTRL410A 6 92 1 19 25 BAYHTRL415A 10 39 TWE100AD TWE100BD 1 27 30 BAYHTRL425A 20 78 2 42 45 BAYHTRL435A 24 22 2 57 60 BAYHTRM410A 6 94 1 21 30 BAYHTRM420A 13 83 TWE155BD 1 36 40 BAYHTRM430A 2...

Page 33: ...5 wires 24 volts to outdoor section A 2 wires 24 volts to outdoor section B 2 wires 24 volts between outdoor sections A B Electric heat add 1 additional wire 24 volts Outdoor thermostat add 1 additio...

Page 34: ...34 SSP PRC002 EN Typical Wiring Heat Pump Heat Pump Single Compressor Typical unit wiring diagram For specific wiring see individual Service Facts...

Page 35: ...35 SSP PRC002 EN Typical Wiring Heat Pump...

Page 36: ...36 SSP PRC002 EN Heat Pump Dual Compressors Typical unit wiring diagram For specific wiring see individual Service Facts Heat Pump Typical Wiring...

Page 37: ...37 SSP PRC002 EN Typical Wiring Heat Pump...

Page 38: ...38 SSP PRC002 EN Typical Wiring Air Handler Air Handler Typical unit wiring diagram For specific wiring see individual Service Facts...

Page 39: ...Figure DD 1 TWA075 Heat Pump All dimensions are in inches and millimeters Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES 914 MM FROM WALLS SHRUBBERY PRIVACY FENCES ETC MINIMUM CLEARANCE B...

Page 40: ...gure DD 2 10TonTWA100A Heat Pump All dimensions are in inches and millimeters Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES 914 MM FROM WALLS SHRUBBERY PRIVACY FENCES ETC MINIMUM CLEARANC...

Page 41: ...Figure DD 3 TWA155B Heat Pump All dimensions are in inches and millimeters Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES 914 MM FROM WALLS SHRUBBERY PRIVACY FENCES ETC MINIMUM CLEARANCE...

Page 42: ...Figure DD 4 TWA200B Heat Pump All dimensions are in inches and millimeters Note 1 MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES 914 MM FROM WALLS SHRUBBERY PRIVACY FENCES ETC MINIMUM CLEARANCE...

Page 43: ...nd attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration Plastic drain pan access plate on the end of unit opposite drain connection must...

Page 44: ...nd attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration Plastic drain pan access plate on the end of unit opposite drain connection must...

Page 45: ...configuration Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning Access plate must be reinstalled after sliding drain pan b...

Page 46: ...r the vertical or horizontal configuration Plastic drain pan access plate on the end of unit opposite drain connection must be removed to slide drain pan out for cleaning Access plate must be reinstal...

Page 47: ...E075A 45 1 8 16 1 11 16 41 15 16 6 5 8 41 3 4 7 16 36 7 8 1146 2 406 4 42 9 1065 2 168 3 1060 5 177 8 406 4 936 6 TWE100A 61 1 8 16 1 11 16 57 15 16 6 5 8 57 13 16 7 16 36 7 8 1552 6 406 4 42 9 1471 6...

Page 48: ...nd attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration Plastic drain pan access plate on the end of unit opposite drain connection must...

Page 49: ...and attached drain connection may be installed on either end of unit in either the vertical or horizontal configuration Plastic drain pan access plate on the end of unit opposite drain connection must...

Page 50: ...4 3 3 4 95 3 TWE200B 89 1 4 2267 1 11 16 42 9 50 13 16 1290 6 11 1 2 292 1 20 1 8 511 2 3 1 16 77 8 39 1 8 993 8 82 7 8 2105 4 9 16 115 9 Table DD 2 Air Handler Dimensions in mm Continued Model No K L...

Page 51: ...SP PRC002 EN Dimensional Data Accessories Figure DD 13 Electric Heater forTWE050 075 100Air Handlers All dimensions are in inches and millimeters Figure DD 14 Electric Heater forTWE155 and 200Air Hand...

Page 52: ...ration and noise by having no suction and discharge valves External high and low pressure cutout devices shall be provided Evaporator defrost control provided in indoor blower coil shall prevent compr...

Page 53: ...ow voltage terminal strip check valve s and single point power entry shall be included All necessary controls shall be factory installed and wired Evaporator defrost control shall be included to preve...

Page 54: ......

Page 55: ......

Page 56: ...s at comfort trane com SinceTrane has a policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Literature Order Number File...

Reviews: