Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler
No.
Stage 1
Stage 2
Total
Unit
Total
of
kW
Btu
kW
kW
Btu
kW
Btu
kW
Model No.
kW
Stages
Input
Output
Output
Input
Output
Output Output
Output
TWE050, 075,100
3.47
1
3.47
11,851
3.47
—
—
—
11,851
3.47
6.92
1
9.92
23,606
6.92
—
—
—
23,606
6.92
10.39
1
10.39
35,457
10.39
—
—
—
35,457
10.39
17.31
2
10.39
35,457
10.39
6.92
23,606
6.92
59,063
17.31
TWE075, 100A, 100
24.22
2
13.83
47,213
13.83
10.39
35,457
10.39
82,670
24.22
TWE155, 200
6.94
1
6.94
23,701
6.94
—
—
—
23,701
6.94
13.83
1
13.83
47,213
13.83
—
—
—
47,213
13.83
20.78
2
13.83
47,213
13.83
6.94
23,701
6.94
70,915
20.78
34,62
2
20.78
70,915
20.78
13.84
47,213
13.89
118,128
34.61
*Heaters are rated at 400v. For other than rated voltage,
Capacity =
Voltage
2
x Rated Capacity and kW =
Voltage
2
x Rated kW.
(
Rated Voltage
)
(
Rated Voltage
)