Initial Setup
20
RMWH-SVX001C-EN
9. Select
Done
to accept the settings and return to the
gas-specific configuration screen, which shows the
updated settings.
10. Repeat
through
until all event setpoints
have been configured.
11. Select the
Points
tab.
12. Select the applicable checkbox to assign a point to the
gas.
Note:
If the
Points
tab is selected but a gas has not
been selected, the options on the
Configure
Gas
screen will be inactive.
Only one gas can be assigned to a single point. Points
that have already been assigned a gas are not available
for selection.
13. Select
Save
.
14. Repeat
for each gas to be
configured.
Note:
The
Reset
tab is not used during the initial
setup. For information about the
Reset
tab,
refer to
15. When all applicable gases have been configured,
select
Next
.
16. The
Initial Setup
screen shows a check mark beside
the
Gas Configuration
step to indicate that it is
complete. Select
Continue
to go to the relay
configuration setup.