Initial Setup
RMWH-SVX001C-EN
21
Relay Configuration
Each relay is mapped to a specific predetermined function;
that is, fault, alarm, warning, caution, or horn.
1. On the
Configure Relays
screen, select
Edit
for the
function to configure.
Note:
The options for the configuration settings for
alarms, warnings, cautions, and the horn are
identical.
The default setting for the internal fault relay is the
energized state. To test the relay, do the following:
•
Select
ON
.
•
Select
OFF
.
2. In the relay configuration pop-up, select the
Name
field, and use the alphanumeric keyboard pop-up to
enter a value.
Relay names can have eight characters.
The title in the pop-up header changes to show the
assigned name.
3. Select
Energized
or
De-energized
for the relay state.
4. Do the following to test the relay:
a. Select
ON
.
b. Make sure the equipment connected to the relay
operates as expected.
c. Select
OFF
.
5. Select
Save
. The updated settings for the relays show
on the
Configure Relays
screen.
6. Repeat
configured.
7. When all relays have been configured, select
Next
.
8. The
Initial Setup
screen shows a check mark beside
the
Relay Configuration
step to indicate that it is
complete. Select
Continue
to go to the output
configuration setup.